User manual

User Manual ADPRO
®
XOa Client Software
104 21796_05_preliminary
To activate an output on input I201, open System > Behaviour > Input/Output behaviour, select an output
(filter on On the box outputs to see only the physical outputs) and choose Programmable. Select Active
sensor (I201) in the list.
All sensors assigned to an alarm profile that triggers I201, have to return to idle state in order to reset the
selected output. When this condition is fulfilled, the user can arm the video system without triggering a false
alarm.
12.4.7 Fire Primary Profile
The fire primary profile is used with fire detection systems. You use it to send alarm messages to all
transmission destinations when a primary fire detection device detects fire. The profile sends messages in
both armed and disarmed states. It sends the alarm message again every 15 minutes as long as the alarm is
active. When the system detects the end of alarm, it does not send a new message indicating that the alarm
is no longer active. Note that you cannot switch off the repeat alarm.
The profile type is 1 Fire primary. Note that you cannot modify the profile type of the standard alarm
profiles.