[FILE NAME]
INTEGRATED AUTOMATION INSTRUMENTATION & TERMINAL
DEVICES FOR ELECTRONIC SAFETY & SECURITY SYSTEMS
25 38 00 - 17
LENEL CONFIDENTIAL INFORMATION For use by Lenel-authorized VARs, prospective or existing Facility Commander users
and their respective authorized consultants. All other third-party use is prohibited without Lenel’s written permission.
f. Outputs
g. Allow assignment to one or multiple facilities
3. Monitor and report alarm conditions:
a. Intrusion Detection Panel
1) Duress code entered
2) Main power failure
3) Panel offline
4) Siren monitor failure
5) Panel tamper
b. Intrusion Data Gathering Panel
1) Panel bypassed
2) Main power failure
3) DGP offline
4) Siren monitor failure
5) Panel tamper
c. Intrusion Keypad
1) Intrusion keypad bypassed
2) Duress alarm
3) Keypad offline
4) Keypad tamper
d. Intrusion Area
1) Failed to arm
2) State armed and in alarm
e. Intrusion inputs
1) Input alarm
2) Input bypassed
3) Fault alarm
4) Tamper alarm
4. Support the following intrusion detection panels
a. Interlogix Alliance ATS 20xx
b. Interlogix Alliance ATS 30xx
c. Interlogix Alliance ATS 40xx
J. Analog CCTV Switcher Management
1. Support network connectivity to analog video switcher
2. Configure to support associated video system
a. Define camera inputs
b. Define video outputs
c. Configure system control commands
1) Define and assign “Enable”, “Disable”, and “Camera Alarm” messages to
system alarms
3. Support the following CCTV matrix switcher interfaces:
a. Interlogix
1) Crosspoint 32 (Kalatel KTD-348)
2) Digiplex IV (Kalatel KTD-440)
b. Pelco
c. Bosch Allegiant
4. Monitor and report alarm conditions:
a. Analog switcher offline