Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Användarhandbok SE Appendix SmartSolar charge controller MPPT 150/35
1. General Description EN NL 1.1 Charge current up to 35A and PV voltage up to 150V The SmartSolar MPPT 150/35 charge controller is able to charge a lower nominal-voltage battery from a higher nominal voltage PV array. The controller will automatically adjust to a 12V, 24V or a 48V nominal battery voltage. ES SE 1.4 Outstanding conversion efficiency No cooling fan. Maximum efficiency exceeds 98%. Full output current up to 40°C (104°F). DE 1.
1.8 Flexible charge algorithm Fully programmable charge algorithm, and eight preprogrammed algorithms, selectable with a rotary switch. 1.9 Adaptive three step charging The SmartSolar MPPT Charge Controller is configured for a three step charging process: Bulk – Absorption – Float. 1.9.1. Bulk During this stage the controller delivers as much charge current as possible to rapidly recharge the batteries. 1.9.2.
EN 1.11 Configuring and monitoring - Bluetooth Smart built-in: the wireless solution to set-up, monitor and update the controller using Apple and Android smartphones, tablets or other devices. - Use the VE.Direct to USB cable (ASS030530000) to connect to a PC, a smartphone with Android and USB On-The-Go support (requires additional USB OTG cable). - Use a VE.Direct to VE.Direct cable to connect to a MPPT Control, a Color Control or the Venus GX.
2. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS - This manual contains important instructions that shall be followed during installation and maintenance. Danger of explosion from sparking Danger of electric shock ● Please read this manual carefully before the product is installed and put into use. ● This product is designed and tested in accordance with international standards. The equipment should be used for the designated application only. ● Install the product in a heatproof environment.
3. Installation DE ES SE Appendix 5 FR 3.2 Grounding ● Battery grounding: the charger can be installed in a positive or negative grounded system. Note: apply a single ground connection (preferably close to the battery) to prevent malfunctioning of the system. ● Chassis grounding: A separate earth path for the chassis ground is permitted because it is isolated from the positive and negative terminal.
WARNING: WHEN A GROUND FAULT IS INDICATED, BATTERY TERMINALS AND CONNECTED CIRCUITS MAY BE UNGROUNDED AND HAZARDOUS. 3.3. PV configuration (also see the MPPT Excel sheet on our website) ● Provide a means to disconnect all current-carrying conductors of a photovoltaic power source from all other conductors in a building or other structure.
Pos 6 7 27,6 32,2 @8% -32 Default setting Gel Victron deep discharge 32,4 28,8 27,6 -32 Gel Exide A200 @8% AGM Victron deep discharge Stationary tubular plate (OPzS) AGM spiral cell 33,0 29,4 27,6 -32 Stationary tubular plate @8% (OPzS) Rolls AGM 33,4 PzS tubular plate traction 29,8 27,6 -32 batteries or @25% OPzS batteries 33,8 PzS tubular plate traction 30,2 27,6 -32 batteries or @25% OPzS batteries 34,2 PzS tubular plate traction 30,6 27,6 -32 batteries or @25% OPzS batteries Lithium Iron Phosphate
On all models with software version V 1.12 or higher a binary LED code helps determining the position of the rotary switch. After changing the position of the rotary switch, the LEDs will blink during 4 seconds as follows: Switch position 0 1 2 3 4 5 6 7 LED Bulk 1 0 0 0 1 1 1 1 LED Abs 1 0 1 1 0 0 1 1 LED Float 1 1 0 1 0 1 0 1 Blink frequency Fast Slow Slow Slow Slow Slow Slow Slow Thereafter, normal indication resumes, as described below.
EN 3.7 Battery charging information The charge controller starts a new charge cycle every morning, when the sun starts shining.
3.8 Automatic equalization Automatic equalization is default set to ‘OFF’. With the Victron Connect app (see sect 1.11) this setting can be configured with a number between 1 (every day) and 250 (once every 250 days). When automatic equalization is active, the absorption charge will be followed by a voltage limited constant current period (see table in section 3.5).
4. Troubleshooting EN Problem Solution Reversed PV connection Connect PV correctly Reverse battery connection Non replacable fuse blown. Return to VE for repair Check battery connection Only for a 24V or 48V system: wrong system voltage chosen by the charge controller Set the controller manually to the required system voltage (see section 1.
5. Specifications SmartSolar charge controller Battery voltage Maximum battery current MPPT 150/35 12/24/48V Auto Select (36V: manual) 35A Nominal PV power, 12V 1a,b) 500W (MPPT range 15V to 130V) Nominal PV power, 24V 1a,b) 1000W (MPPT range 30V to 130V) Nominal PV power, 48V 1a,b) 2000W (MPPT range 60V to 130V) Max.
EN Figure 1: Power connections NL FR DE ES SE Appendix
Distributor: Serial number: Version Date : 07 : September 21st, 2018 Victron Energy B.V. De Paal 35 | 1351 JG Almere PO Box 50016 | 1305 AA Almere | The Netherlands General phone E-mail www.victronenergy.com : +31 (0)36 535 97 00 : sales@victronenergy.