Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Användarhandbok SE Appendix BlueSolar charge controllers MPPT 75/10 MPPT 75/15 MPPT 100/15
EN 1 General Description NL 1.1 Ultra fast MPPT tracking Especially in case of a clouded sky, when light intensity is changing continuously, a fast MPPT algorithm will improve energy harvest by up to 30% compared to PWM charge controllers and by up to 10% compared to slower MPPT controllers. FR 1.2 VE.Direct For a wired data connection to a Color Control panel, PC or other devices DE 1.3 Load output Deep discharge of the battery can be prevented by connecting all loads to the load output.
1.7 Three step charging The controller is configured for a three step charging process: Bulk – Absorption - Float. See section 3.8 and section 5 for default settings. See section 1.8 for user defined sttings 1.7.1. Bulk During this stage the controller delivers as much charge current as possible to rapidly recharge the batteries. 1.7.2. Absorption When the battery voltage reaches the absorption voltage setting, the controller switches to constant voltage mode.
EN 2. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS - This manual contains important instructions that shall be followed during installation and maintenance. NL Danger of explosion from sparking FR Danger of electric shock ES SE Appendix 3 DE ● It is advised to read this manual carefully before the product is installed and put into use. ● This product is designed and tested in accordance with international standards. The equipment should be used for the designated application only.
3. Installation WARNING: DC (PV) INPUT NOT ISOLATED FROM BATTERY CIRCUIT CAUTION: FOR PROPER TEMPERATURE COMPENSATION THE AMBIENT CONDITION FOR CHARGER AND BATTERY MUST BE WITHIN 5°C. 3.1. General ● Mount vertically on a non-flammable substrate, with the power terminals facing downwards. Observe a minimum clearance of 10 cm under and above the product for optimal cooling. ● Mount close to the battery, but never directly above the battery (in order to prevent damage due to gassing of the battery).
● Maximum open circuit PV voltage: 75V respectively 100V EN NL For example: 12V battery and mono- or polycristalline panels connected to a 75V controller ● Minimum number of cells in series: 36 (12V panel). ● Recommended number of cells for highest controller efficiency: 72 (2x 12V panel in series or 1x 24V panel). ● Maximum: 108 cells (3x 12V panel in series).
Some loads with high inrush current can best be connected directly to the battery. If equipped with a remote on-off input, these loads can be controlled by connecting the load output of the controller to this remote on-off input. A special interface cable may be needed. Alternatively, a BatteryProtect may be used to control the load. Please see our website for specifications. Low power inverters, such as the Phoenix VE.
EN 3.8 Battery charging information The charge controller starts a new charge cycle every morning, when the sun starts shining.
4.
BlueSolar charge controller MPPT 75/10 MPPT 75/15 Battery voltage MPPT 100/15 12/24V Auto Select 15A 145W 220W 220W Nominal PV power, 24V 1a,b) 290W 440W 440W 13A 15A 15A Max.
EN Figure 1a: configuration pins of the VE.Direct communication port, 75V models NL FR DE ES SE Appendix Figure 1b: pin numbering of the VE.Direct communication port.
Figure 2a: configuration pins of the VE.Direct communication port, 100V model Figure 2b: pin numbering of the VE.
Figure 3: Battery management options EN FR EN: Bridge between pin 1 and 2: Low voltage disconnect: 11.1V or 22.2V Automatic load reconnect: 13.1V or 26.
Figure 4: Power connections Figure 5: The Victron inverters model Phoenix 12/800, 24/800, 12/1200 and 24/1200 can be controlled by connecting the right side connection (1) of the inverter remote control directly to the solar charger load output. Similarly, all Phoenix VE.
Victron Energy Blue Power Distributor: Serial number: Version : 05 th Date : July 24 , 2018 Victron Energy B.V. De Paal 35 | 1351 JG Almere PO Box 50016 | 1305 AA Almere | The Netherlands General phone : +31 (0)36 535 97 00 E-mail : sales@victronenergy.com www.victronenergy.