VE.Bus device menu
Current device Setting Selects the device to communicate with for
configuration options, and values in the
“Device specific” menu.
Flash LEDs Setting Flash the LEDs on the device selected with
the “Current device” property.
System defaults Setting Restore all target settings to their default
values.
VE.Bus sys setup Setting The current configuration of the VE.Bus
system. See chapter 6.5 - VE.Bus system
configuration for more information.
General menu
Sys. frequency Setting The frequency of the mains supply in your
region.
Transfer switch menu
Wide input freq. Setting Allows the A.C. input frequency to be
anywhere from 45 – 65 Hz.
Ground relay Setting Enable this for systems with an earth leakage
circuit breaker.
AC low discon. Setting The voltage at which the transfer switch will
disconnect the A.C. supply, and switch to the
inverter.
AC low connect Setting The voltage above the disconnect voltage at
which the transfer switch will re-connect the
A.C.
AC high discon. Setting See “AC low discon.”
AC high connect Setting See “AC low connect”
UPS function Setting Enables or disables the fast checking of the
A.C. waveform. Disabling this will result in
slower transfer speeds, but will be more
tolerant of poor input signals.
Dyn. Cur. lim. Setting When enabled, the inverter will be started if
the load increases rapidly, to avoid voltage
drops as the generator adjusts to the new
load.
Default cur lim Setting The value that will be used for the shore
current limit if no VVC or remote panel is
connected to the target.
Inverter menu
Inverter voltage Setting The desired output voltage of the inverter.
DC low shutdown Setting The inverter will switch off when the battery
voltage drops to this level.
DC low restart Setting The inverter will restart when the battery
voltage rises this far above the shutdown
voltage.