3. Charge algorithms 
3.1 Smart charge algorithm with optional reconditioning for 
 lead-acid batteries 
Charge voltages at room temperature: 
MODE 
ABS 
V 
FLOAT 
V 
STORAGE 
V 
RECONDITION 
Max V@% of Inom 
NORMAL 
14,4 
13,8 
13,2 
16,2@8%, max 1h 
HIGH 
14,7 
13,8 
13,2 
16,5@8%, max 1h 
LI-ION 
14,2 
13,5 
13,5 
n. a. 
For 24V chargers: multiply all voltage values by 2. 
NORMAL (14,4V): recommended for flooded flat plate lead 
antimony batteries (starter batteries), flat plate gel and AGM 
batteries. 
HIGH (14,7V): recommended for flooded lead calcium batteries, 
Optima spiral cell batteries and Odyssey batteries. 
Eight step charge sequence for lead-acid batteries: 
1.  CHARGE/TEST 
Tests if the battery can accept charge, even if the battery is 
fully discharged (zero or nearly zero Volt across the 
terminals). 
All charge status LEDs will flash in case of reverse polarity 
connection, short-circuit or if a 12V charger is connected to 
a 24V battery. 
The TEST LED will flash as long as a charge pulse does 
not increase battery voltage to more than 12,5V resp. 25V. 
If the flashing persists during several minutes the battery is 
probably damaged (internal short-circuit): disconnect the 
charger. 
A false rejection may occur if a load is simultaneously 
draining a very weak or fully discharged battery during the 
test phase: disconnect the load and repeat the test. 