Product Manual
Victron Energy bv / De Paal 35 / 1351 JG ALMERE / The Netherlands 
Phone: (+31) (0)36 535 97 00 / www.victronenergy.com / e-mail: sales@victronenergy.com 
BMS12/200  
ENGLISH 
1. Mount the BMS preferably on a vertical surface, for optimal 
cooling. 
2. Determine the rating of fuse AB (see figure and table 1). 
The fuse on input AB doubles as a shunt. The BMS will limit the 
input current according to the rating of this fuse. For fuse ratings 
and corresponding current limit please see table 1. 
Choosing the right fuse will prevent overheating of the alternator 
and/or DC cabling. 
3. Determine the rating of fuse LB (see figure). 
This fuse should be rated in accordance with the expected load 
current and the cross section of the cabling to the load. 
4. Disconnect the cabling from the plus pole of the starter battery. 
5. Pull off the REMOTE on/off connector to prevent unwanted 
switching of the BMS. 
6. Install and connect all electrical cabling and fuses AB, LB, but 
leave the plus poles of the Li-ion batteries and starter battery 
disconnected. 
7. Daisy-chain the battery control cables between the Li-ion batteries 
and connect to the BMS. 
8. Connect the plus cabling to the Li-ion batteries and the starter 
battery. 
9. Reinsert the REMOTE on/off connector on the BMS. 
The BMS is now ready for use. 
Notes: 
a) A battery charger can be connected to input AB instead of the 
alternator. 
b) The Li-ion batteries can be charged as well as discharged through 
input/output LB. 
c) When a load with a large electrolytic capacitor bank (such as an 
inverter or inverter/charger rated at 1200VA or more) is connected 
to LB, the BMS will limit its average output current during start-up 
to approximately 80A. Therefore the capacity to simultaneously 
start-up other DC loads is limited to 80A. Once the capacitor bank 
is fully charged, the current limit increases to 400A.
BMS 12/200 specification 
Maximum number of 12,8V batteries 
10 
Maximum charge current, Power Port AB 
80A @ 40°C 
Maximum charge current, Power Port LB 
200A @ 40°C 
Maximum continuous discharge current, LB 
200A @ 40°C 
Peak discharge current, LB (short circuit proof) 
400A 
Approximate cut-off voltage 
11V 
GENERAL 
No load current when operating 
10mA 
Current consumption when switched off 
5mA 
Current consumption after battery discharge 
cut-off due to low cell voltage 
3mA 
Operating temperature range 
-40 to +60°C 
Humidity, maximum 
100% 
Humidity, average 
95% 
Protection, electronics 
IP65 
DC connection AB, LB and battery minus 
M8 
DC connection battery plus 
Faston female 
6.3 mm 
LED’s 
Battery being charged through Power Port AB 
green 
Battery being charged through Power Port LB 
green 
Power port LB active 
green 
Over temperature 
red 
ENCLOSURE 
Weight (kg) 
1.8 
Dimensions (hxwxd in mm) 
65 x 120 x 260 
STANDARDS 
Emission 
EN 50081-1 
Immunity 
EN 50082-1 
Automotive Directive 
2004/104/EC 
Revision  : Rev 04 
Date  : 18-05-2020 
Table 1 
If the required charge current 
(input AB) is less than 40 A, 
please use this ATO fuse holder 
Fuse AB  Max. charge current 
100 A 
90 A 
80 A 
70 A 
60 A 
40 A 
2 x 30 A  35 A 
2 x 20 A  25 A 
2 x 15 A 
20 A 
2 x 10 A 
18 A 
2 x 7.5 A 
12 A 