User manual

-10-
goes over 100%
Loss of AC power Generates an alarm if
the AC voltage drops
below the specified
value.
“alarm disabled”,
“alarm enabled”,
“shutdown enabled”
“alarm enabled”
Gen failure Generates an alarm if
multiple failures are
detected.
”alarm disabled”,
“alarm enabled”
“alarm enabled”
Gen underload Generates an alarm if
the generator has
been running at less
than the specified
load for more than the
specified duration.
“pre alarm off”, “pre
alarm on”, “pre
shutdown on”
“pre alarm off”
Under speed Generates an alarm if
the generator drops
below 90% of the
nominal engine
speed.
“alarm disabled”,
“alarm enabled”
“alarm enabled”
Over speed Generates an alarm if
the generator rises
over 110% of the
nominal engine
speed.
“pre alarm off”, “pre
alarm enabled”, “pre
shutdown enabled”
“pre alarm enabled”
Service due 25hr Generates an alarm
25 hours before the
next service is due.
“alarm disabled”,
“alarm enabled”
“alarm enabled”
4.2 Generator setup
This menu contains all of the generator specific settings. It is important to ensure that these
setting reflect the characteristics of the generator.
Note: Values for the alarm set-points will only be used if the corresponding alarm is enabled (see
chapter 4.1 - Generator alarms)
Gen setup menu
Menu item Description Range Step
size
Default
value
Generator
type
The type of generator that is
connected. This determines the
start up and shutdown
procedures. Configurations for
other generator types are
available on request.
“Northern Lights”
(standard),
“Northern L AS”
(Northern Lights
auto start),
“Vetus”,
“Westerbeke”,
“Kohler small”,
“Kohler large”,
“Mase”, “Fischer
Panda”
N/A “Northern
Lights”
Gen nom
voltage
The nominal A.C. output voltage
of the generator.
110V/230V N/A 230V
Gen
frequency
The nominal output frequency
and engine speed for the
“50Hz – 1500rpm”,
“50Hz – 3000rpm”,
N/A “50Hz –
1500rpm”