Technical information

41
SKYLLA CHARGER 24/48V
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40
E-mail: sales@victronenergy.com | www.victronenergy.com
Skylla
24/30 TG
24/50 TG
24/50 TG
3 phase
24/80 TG 24/100 TG
24/100 TG
3 phase
48/25 TG 48/50 TG
Input voltage (V AC) 230 3 x 400 230 230 3 x 400 230 230
Input voltage range (V AC) 185-264 320-450 185-264 185-264 320-450 185-264 185-264
Input voltage range (V DC) 180-400 n. a. 180-400 180-400 n. a. 180-400 180-400
Frequency (Hz) 45-65
Power factor 1
Charge voltage 'absorption' (V DC) 28,5 28,5 28,5 28,5 28,5 57 57
Charge voltage 'float' (V DC) 26,5 26,5 26,5 26,5 26,5 53 53
Charge current house batt. (A) (2) 30 / 50 50 80 100 100 25 50
Charge current starter batt. (A) 4 4 4 4 4 n. a. n. a.
Charge characteristic IUoUo (three step)
Battery capacity (Ah) 150-500 250-500 400-800 500-1000 500-1000 125-250 250-500
Temperature sensor
Can be used as power supply
Remote alarm Potential free contacts 60V / 1A (1x NO and 1x NC)
Forced cooling
Protection (1) a,b,c,d
Operating temp. range -20 to 60°C (0 - 140°F)
Humidity (non condensing) max 95%
ENCLOSURE
Material & Colour aluminium (blue RAL 5012)
Battery-connection M8 studs
230 V AC-connection screw-clamp 2,5 mm² (AWG 6)
Protection category IP 21
Weight kg (lbs) 5,5 (12.1) 13 (28) 10 (22) 10 (22) 23 (48) 5,5 (12.1) 10 (12.1)
Dimensions hxwxd in mm
(hxwxd in inches)
365x250x147
(14.4x9.9x5.8)
365x250x257
(14.4x9.9x10.1)
365x250x257
(14.4x9.9x10.1)
365x250x257
(14.4x9.9x10.1)
515x260x265
(20x10.2x10.4)
365x250x147
(14.4x9.9x5.8)
365x250x257
(14.4x9.9x10.1)
STANDARDS
Safety EN 60335-1, EN 60335-2-29
Emission EN 55014-1, EN 61000-3-2
Immunity EN 55014-2, EN 61000-3-3
1) Protection
a. Output short circuit
b. Battery reverse polarity detection
2) Up to 40°C (100°F) ambient
c. Battery voltage too high
d. Temperature too high
BMV 600S Battery Monitor
The BMV 600S Battery Monitor features an advanced
microprocessor control system combined with high
resolution measuring systems for battery voltage and
charge/discharge current. Besides this, the software
includes complex calculation algorithms, like
Peukert’s formula, to exactly determine the state of
charge of the battery. The BMV 600S selectively
displays battery voltage, current, consumed Ah or
time to go.
Skylla Control
The Skylla Control allows you to alter the charge
current and see the system status. Altering the charge
current is useful if the shore power fuse is limited: the
AC current drawn by the battery charger can be
controlled by limiting the maximum output current,
thereby preventing the shore power fuse from
blowing.
Charger Switch
A remote on-off switch
Battery Alarm
An excessively high or low battery voltage is
indicated by an audible and visual alarm.