SKYLLAI BATTERY CHARGER 24V
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40
E-mail: sales@victronenergy.com | www.victronenergy.com
Skylla-i 24/80 (1+1) 24/80 (3) 24/100 (1+1) 24/100 (3)
Input voltage (VAC) 230 V
Input voltage range (VAC) 185-265 V
Input voltage range (VDC) 180-350 V
Maximum AC input current @ 180 VAC 16 A 20 A
Frequency (Hz) 45-65 Hz
Power factor 0,98
Charge voltage 'absorption' (VDC)
(1)
28,8 V
Charge voltage 'float' (VDC) 27,6 V
Charge voltage ‘storage’ (VDC) 26,4 V
Charge current (A)
(2)
80 A
3 x 80 A
(max total output: 80A)
100 A
3 x 100 A
(max total output: 100A)
Charge current starter batt. (A) 4 A n. a. 4 n. a.
Charge characteristic 7 stage adaptive
Battery capacity (Ah) 400-800 Ah 500-1000 Ah
Charge curve, Li-Ion 4 stage, with on-off control or Can bus control
Temperature sensor Yes
Can be used as power supply Yes
Remote on-off port Yes (can be connected to a Li-Ion BMS)
CAN bus communication port Two RJ45 connectors, NMEA2000 protocol, galvanically isolated
Remote alarm relay DPST AC rating: 240VAC/4A DC rating: 4A up to 35VDC, 1A up to 60VDC
Forced cooling Yes
Protection Battery reverse polarity (fuse) Output short circuit Over temperature
Operating temp. range -20 to 60°C (Full output current up to 40°C)
Humidity (non condensing) max 95%
ENCLOSURE
Material & Colour aluminium (blue RAL 5012)
Battery-connection M8 bolts
230 VAC-connection screw-clamp 10mm² (AWG 7)
Protection category IP 21
Weight kg (lbs) 7 kg (16 lbs)
Dimensions hxwxd in mm
(hxwxd in inches)
405 x 250 x 150 mm
(16.0 x 9.9 x 5.9 inch)
STANDARDS
Safety EN 60335-1, EN 60335-2-29
Emission EN 55014-1, EN 61000-6-3, EN 61000-3-2
Immunity EN 55014-2, EN 61000-6-1, EN 61000-6-2, EN 61000-3-3
1) Output voltage range 20-36V.
Can be set with rotary switch or
potentiometers.
2) Up to 40°C (100°F) ambient.
Output will reduce to 80% at 50°C, and to 60% at 60°C.
BMV 600S Battery Monitor
The BMV 600S Battery Monitor features an
advanced microprocessor control system
combined with high resolution measuring
systems for battery voltage and
charge/discharge current.
The software includes complex calculation
algorithms, like Peukert’s formula, to exactly
determine the state of charge of the battery.
The BMV 600S selectively displays battery
voltage, battery current, consumed Ah or
time to go.
Skylla-i Control
The Skylla-i Control panel provides remote
control and monitoring of the charge process
with LED status indication. In addition, the
remote panel also offers input current
adjustment that can be used to limit the input
current and thus the power drawn from the AC
supply. This is particularly useful when
operating the charger from limited shore
power or small gensets. The panel can also be
used to change several battery charging
parameters.