Datasheet

64
www.victronenergy.com
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40
E-mail: sales@victronenergy.com | www.victronenergy.com
BlueSolar charge controller MPPT 150/35
Battery voltage
12 / 24 /48 V Auto Select
(software tool needed to select 36 V)
Rated charge current 35 A
Maximum PV power, 12V 1a,b) 12V: 500W / 24V: 1000W / 36V: 1500W / 48V: 2000W
Maximum PV open circuit voltage
150V absolute maximum coldest conditions
145V start-up and operating maximum
Maximum efficiency 98 %
Self-consumption
0,0o1 mA (1 µA)
Charge voltage 'absorption' Default setting: 14,4 / 28,8 / 43,2 / 57,6 V
Charge voltage 'float' Default setting: 13,8 / 27,6 / 41,4 / 55,2 V
Charge algorithm multi-stage adaptive
Temperature compensation -16 mV / °C resp. -32 mV / °C
Protection
Battery reverse polarity (fuse)
PV reverse polarity
Output short circuit
Over temperature
Operating temperature -30 to +60°C (full rated output up to 40°C)
Humidity 95 %, non-condensing
Data communication port
VE.Direct
See the data communication white paper on our website
ENCLOSURE
Colour Blue (RAL 5012)
Power terminals 13 mm² / AWG6
Protection category IP43 (electronic components), IP22 (connection area)
Weight 1,25 kg
Dimensions (h x w x d) 130 x 186 x 70 mm
1a) If more PV power is connected, the controller will limit input power to 700W resp. 1400W
1b) PV voltage must exceed Vbat + 5V for the controller to start.
Thereafter minimum PV voltage is Vbat + 1V
Charge current up
to 35 A and PV voltage up to 150
V
The BlueSolar charge controller will charge a lower nominal-voltage battery with a higher
nominal voltage PV array.
The controller will automatically adjust to 12 V, 24 V or 48 V nominal battery voltage.
(software tool needed to select 36 V)
Ultra-fast Maximum Power Point Tracking (MPPT)
Especially in case of a clouded sky, when light intensity is changing continuously, an ultra-fast
MPPT controller will improve energy harvest by up to 30% compared to PWM charge controllers
and by up to 10% compared to slower MPPT controllers.
Advanced Maximum Power Point Detection in case of partial shading conditions
If partial shading occurs, two or more maximum power points may be present on the power-
voltage curve.
Conventional MPPT’s tend to lock to a local MPP, which may not be the optimum MPP.
The innovative BlueSolar algorithm will always maximize energy harvest by locking to the
optimum MPP.
Outstanding conversion efficiency
No cooling fan. Maximum efficiency exceeds 98%. Full output current up to 40°C (104°F).
Flexible charge algorithm
Fully programmable charge algorithm (see the software page on our website), and eight
preprogrammed algorithms, selectable with a rotary switch (see manual for details).
Extensive electronic protection
Over-temperature protection and power derating when temperature is high.
PV short circuit and PV reverse polarity protection.
PV reverse current protection.
Internal temperature sensor
Compensates absorption and float charge voltages for temperature.
BlueSolar charge controller MPPT 150/35
Maximum Power Point Tracking
Upper curve:
Output current (I) of a solar panel as function of
output voltage (V).
The maximum power point (MPP) is the point
Pmax along the curve where the product I x V
reaches its peak.
Lower curve:
Output power P = I x V as function of output
voltage.
When using a PWM (not MPPT) controller the
output voltage of the solar panel will be nearly
equal to the voltage of the battery, and will be
lower than Vmp.
Solar charge controller
MPPT 150/35