Datasheet

55
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40
E-mail: sales@victronenergy.com | www.victronenergy.com
Battery monitor BMV 700
BMV 702
BMV 702
BLACK
BMV 700HS
Supply voltage range 6,5 - 95 VDC 6,5 - 95 VDC 60 – 385 VDC
Current draw, back light off < 4 mA < 4 mA < 4 mA
Input voltage range, auxiliary battery n.a. 6,5 - 95 VDC n.a.
Battery capacity (Ah) 20 - 9999 Ah
Operating temperature range -20 +50°C (0 - 120°F)
Measures voltage of second battery, or
temperature, or midpoint
No Yes No
Temperature measurement range -20 +50°C n.a.
VE.Direct communication port Yes Yes Yes
Relay 60V/1A normally open (function can be inverted)
RESOLUTION & ACCURACY (with a 500 A shunt)
Current ± 0,01 A
Voltage ± 0,01 V
Amp hours ± 0,1 Ah
State of charge (0 – 100 %) ± 0,1 %
Time to go ± 1 min
Temperature (0 - 50°C or 30 - 120°F) n. a.
± 1 °C/°F
n. a.
Accuracy of current measurement ± 0,4 %
Accuracy of voltage measurement ± 0,3 %
INSTALLATION & DIMENSIONS
Installation Flush mount
Front 63 mm diameter
Front bezel 69 x 69 mm (2.7 x 2.7 inch)
Body diameter 52mm (2.0 inch)
Body depth 31mm (1.2 inch)
STANDARDS
Safety EN 60335-1
Emission / Immunity EN 55014-1 / EN 55014-2
Automotive ECE R10-4 / EN 50498
ACCESSORIES
Shunt (included) 500 A / 50 mV
Cables (included)
10 meter 6 core UTP with RJ12 connectors,
and cable with fuse for ‘+’ connection
Temperature sensor Optional (ASS000100000)
Color Control
The powerful Linux computer, hidden
behind the color display and buttons,
collects data from all Victron equipment and
shows it on the display. Besides
communicating to Victron equipment, the
Color Control communicates through
NMEA2000, Ethernet and USB.
Data can be stored and analyzed on the VRM
Portal. iPhone and Android apps are
available for monitoring and control.
1000A/50mV and 2000A/50mV shunt
For ease of use with the BMV series: the quick connect PCB on the
standard 500A/50mV shunt
can also be mounted on these shunts.
Victron Global Remote
The Global Remote is a modem which sends alarms,
warnings and system status reports to cellular phon
es via
text messages (SMS). It can also log data from Victron
Battery Monitors, MultiPlus units, Quattros and Inverters
to a website through a GPRS connection to the VRM
Portal. Access to this website is free of charge.
VE.Direct to Global remote Interface cable needed
(ASS030534000).
Interface cables
- VE.Direct cables to connect a BMV 70x to the Color Control (ASS030530xxx)
- VE.Direct to USB interface (ASS030530000) to connect several BMV 70x to the Color Control or
to a computer.
-VE.Direct to Global remote interface to connect a BMV 70x to a Global Remote.
(ASS030534000)
The PC application software BMV-Reader will show all current readings on a computer,
including history data. It can also log the data to a CSV formatted file. It is available for free,
and can be downloaded from our website at the Support and downloads section. Connect
the BMV to the computer with the VE.Direct to USB interface, ASS030530000.
A maximum of four BMVs can be connected directly to the Color Control.
Even more BMVs can be connected to a USB Hub for central monitoring.
Battery Balancer (BMS012201000)
The Battery Balancer equalizes the state of
charge of two series connected 12 V batteries, or
of several parallel strings of series connected
batteries.
When the charge voltage of a 24 V battery
system increases to more than 27 V, the Battery
Balancer will turn on and compare the voltage
over the two series connected batteries. The
Battery Balancer will draw a current of up to 1 A
from the battery (or parallel connected
batteries) with the highest voltage. The resulting
charge current differential will ensure that all
batteries will converge to the same state of
charge.
If needed, several balancers can be paralleled.
A 48 V battery bank can be balanced with three
Battery Balancers.
BMV-700 series: Precision battery monitoring