Specification

©Slant/Fin Corp. 2010. Printed in the U.S.A. 310. Publication No. VSPH-10.
RATINGS FOR WATER
CSA D.O.E. NET I=B=R NET
MODEL
INPUT CAPACITY WATER WATER EFFICIENCY
No.
(Btuh) (Btuh) (Btuh)† (Sq. ft)‡ (A.F.U.E.)
VSPH-60
VSPH-NDV60 60,000 52,000 45,000 300 86.1%
VSPH-90
VSPH-NDV90 90,000 78,000 68,000 453 85.7%
VSPH-120
VSPH-NDV120 120,000 103,000 90,000 600 85.5%
VSPH-150
VSPH-NDV150 150,000 128,000 111,000 740 85.2%
VSPH-180
VSPH-NDV180 180,000 154,000 134,000 893 85.1%
Dimensions VSPH-60 VSPH-90 VSPH-120 VSPH-150 VSPH-180
“A 11
1
8" 14
1
8" 17
1
8" 20
1
8" 23
1
8"
“B 17
3
8" 20
3
8" 23
3
8" 26
3
8" 29
3
8"
Pressure relief
valve
1
1
2" FPT
supply
Install manual main
shutoff valve 5' above
floor when required by
local code
3
4" to air eliminating
system
Dotted gas piping
by others
3" dia.
vent
connector
Press/temp
gauge
Junction
box
1
1
2" return tapping
1
1
4" cir. flange
Vent
connector
28
1
2
"
(See note)
28
3
4"
(See note)
3
4" Drain
25
1
8"
(See note)
A
Jacket
B
Sediment
trap
required
30
1
2"
(See note)
RIGHT SIDE
LEFT SIDE
FRONT
NOTE: Height dimensions increase by 1
1
2" and
depth increases to 28
1
2" when combustible floor
kit is used.
† Ratings must be reduced by 4% at 2,000 feet elevation and an additional 4% for every
additional 1,000 feet elevation over 2,000 feet. Net ratings shown include allowance from
normal piping loss and pick-up load. For installations having unusual piping and pick-up
requirements, additional allowances should be made before selecting the size of boiler
required. Ratings are based on a piping and pick-up factor 1.15.
‡ Based on heat emission rate of 150 Btu per square foot.
Note: All VSPH boilers are tested and rated for capacity under the U.S. Dept. of Energy
(D.O.E.) Test Procedure for Boilers
Maximum ASME working pressure: 50 psi..
PACKAGED WATER BOILER includes pre-assembled cast-iron heat
exchanger with built-in air eliminator, base, pre-assembled insulated flush
jacket, gas burners, gas orifices and manifold assembly, combination gas
valve, including manual shut-off, pressure regulator and pilot adjustment,
integrated boiler control with built-in diagnostics, electronic intermittent pilot
ignition system, pressure and temperature gauge, pressure relief valve
(ASME), circulator 1-1/4", drain cock, inducer assembly, air flow proving
switch, built-in condensate drain, trap and stainless steel vent pipe adapter,
unitized vent/air intake terminal, rollout safety switch. For propane, specify
when ordering.
OPTIONAL EQUIPMENT: Air package consisting of diaphragm expansion
tank, fill and pressure reducing valve, and automatic air vent. Combustible
floor kit. AL 29-4C
stainless steel venting material.
Equipment
Dimensions
Ratings
Before purchasing this appliance
read important energy costs
and efficiency information
available from your contractor.
Supply water tapping 1
1
2"
Circulator return flange* 1
1
4"
Gas tapping, natural or propane
1
2"
AL 29-4C is a registered trademark of Allegheny Ludlum Corp. *When not equipped with circulator, boiler 1
1
2" return tapping.
Victory VSPH boiler minimum
clearances for combustible
construction
(See installation instructions for further details.)
RATINGS FOR NATURAL AND L.P. GAS
VICTORYVSPH
SEALED COMBUSTION GAS BOILER
and
VSPH-NDV POWER VENT BOILER
MAXIMUM EQUIVALENT FLUE LENGTH
VSPH-60, 90 & 120: 40 ft.
VSPH-150: 35 ft.
VSPH-180: 33 ft.
VSPH-NDV 60, 90 & 120: 40 ft.
VSPH-NDV 150: 35 ft.
VSPH-NDV 180: 33 ft.
May differ for certain vent system manufacturers and
altitudes. Vent terminal does not effect calculation
of total equivalent length.
See installation instructions, Pub. VSPH-40.
12"
6"
6"
12"
*2"
6"
*2"
* 6" for
enclosed
(A and B dimensions are the same for VSPH-NDV models)
SLANT/FIN CORPORATION, Greenvale, NY 11548 Phone: (516) 484-2600
FAX: (516) 484-5921 In Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com