User guide

6
USER PARAMETERS
*Refer to the "PARAMETER ACCESS & ADJUSTMENT" section on page 5.
Label Name
Refrigerator Setting
Factory Preset
Freezer Setting
Factory Preset
Unit Minimum Maximum
Measure Input Configuration Parameters
CA1 Cabinet probe offset 0 -1 °F -25 25
This parameter can be used to calibrate the digital display.
P2 Celsius/Fahrenheit °F °F - °C (0) °F (1)
This parameter is used to change the temperature scale.
Main Regulator Parameters
r4 ENERGY SAVING setpoint (relative) 2 4 °F 0 99
This parameter is used to set the increase in setpoint when in ENERGY SAVING mode. See also "i10" parameter on next page.
r5 Overcooling setpoint 5 10 °F 0 99
This parameter is used to set the decrease in setpoint for "SUPER COOL MODE".
r6 Overcooling timeout 30 30 min 0 240
This parameter is used to set the length of time for "SUPER COOL MODE".
Compressor Protection Parameters
C6 Setpoint alarm COH 127 119 °F 0 199
This parameter is used to set the temperature of the COH alarm.
Defrost Parameters
d0 Defrost Interval 12 8 h 0 99
This parameter is used to set the defrost interval.
d8 Kind of Defrost Interval (0) Time (0) Time - (0) Time (4) Calendar
This parameter is used to set the type of defrost interval. If real time defrost interval is required, set this to: (4) Calendar. The Hd parameters must be set to
the time defrosts are required.
d20
Max Time for Safety Defrost in Normal
Operation
N/A 120 - 0 500
This parameter is used to set the time if the compressor runs constantly so that a defrost will initiate.
Temperature Alarms Parameters
A1 Threshold minimum temperature alarm 30 -15 °F -99 99
This parameter is used to set the threshold for the low temperature alarm.
A4 Threshold maximum temperature alarm 50 32 °F -99 99
This parameter is used to set the threshold for the high temperature alarm.
A7 Alarm Delay 15 15 min 0 240
This parameter is used to set a time delay for the high and low temperature alarms.
A8 End of Defrost Time Delay - 30 min 0 240
This parameter is used to set a time delay for the high and low temperature alarms after defrost terminates.
Evaporator Fan(s) Parameters
F0 Fans activity during normal operation (4)THERMO_IF_CMP_ON N/A °F (0) OFF (5) rhL_rhH
This parameter is used to set the fan speed of the refrigerator evaporator fan(s) in the off cycle of the compressor. The factory preset is to run the fans at low
speed during the off-cycle. To set to high speed in the off-cycle, set this parameter to (1) ON
Digital Inputs Parameters
i2 Door Alarm Delay 5 5 min -1 120
This parameter is used to set the time length of door opening that will trigger an "id" alarm (door ajar).
*Parameters Table continued on next page