UG:105 vicorpower.com Applications Engineering: 800 927.9474 Page 17
Signal Ground (J10-10)
Signal Ground (see Figure 4 and Connector Pin Identification on page 14) is an isolated
ground reference for all J10 interfacing signals, and can be used for ConverterPAC
output status signals such as Power Good. This is not the same as Earth Ground on input
power connector J9.
Enable/Disable (J10-1 to J10-8)
The Enable/Disable control pins allow ConverterPAC outputs to be sequenced either
on or o. J10-1 through J10-8 are the control pins for output positions 1 through 8,
respectively (see Figure 5 and Connector Pin Identification on page 14). For DualPACs
and FlexPACs, all outputs are sequenced. In parallel array using VI/VE modules only
the driver ConverterPAC need be controlled. The Enable/Disable pins should be pulled
low to less than 0.7 V with respect to Signal Ground to disable the outputs. They will
sink 10 mA maximum. These pins should be open circuited or allowed to exceed 4.5 V
when enabled. Do not apply more than 6 V to these inputs at any time. If driven from
an electromechanical switch or relay, a capacitor should be connected to eliminate the
eects of switch bounce.
Figure 4.
Interface Connector
12
1110
9
8
7
65
43
2
1
J10
J10-9
J10-10
J10-11
J10-12
Vcc +5V, 0.3A
SIGNAL GROUN
D
AC POWER OK
GEN SHUTDOWN
J10-1
J10-2
J10-3
J10-4
J10-5
J10-6
J10-7
J10-8
E/D-1
E/D-2
E/D-3
E/D-4
E/D-5
E/D-6
E/D-7
E/D-8
Figure 5.
Enable/Disable and
General Shutdown
PFC MegaPAC
1
10
12
Signal Ground
General Shutdown
Enable/Disable Output 1
J10
1
0
TTL "1" (OFF)
TTL "0" (ON)
A TTL "1" applied to the base of the transistor turns
output OFF. Pin 1 (or Pin 12 for GSD) is pulled Low
with respect to Signal Ground.
9
Vcc