User guide
UG:115 vicorpower.com Applications Engineering: 800 927.9474 Page 18
10K
Signal Ground
AC Power OK
+5V
J3
2.49K
PN2222
Pin 4
Pin 6
Bus
Monitor
Figure 10.
AC OK
Auxiliary V
CC
+5 V/0.3 A (J3-5)
The V
CC
on J3-5 is an auxiliary 5 V regulated power source. It is +5 Vdc +/–5% with
respect to Signal Ground and can supply 300 mA maximum. It is short-circuit-proof, but
if shorted, all outputs will shut down through the Enable/Disable circuitry.
Single Output Power Supplies (Arrays)
Vicor’s standard configuration for single output power supplies is to set the le module
(as seen from looking at the power supply output) as the controlling module of the
array.
78M05
Auxiliary Vcc
J3-5
0.1 µF
Signal Ground
J3
J3-4
+5V/300 mA
Figure 11.
Auxiliary Vcc