User Guide

50
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-01 www.viconics.com April 2015
© 2015 Viconics Technologies. All rights reserved.
VT8600 SeriesUser Interface Guide
TEST OUTPUTS
Note: screen Test outputs are LIVE. Any output gets displayed immediately for any value change according to the following:
1. If any BACnet priority array (1 - 16) includes a value, the displayed state background shows in red.
2. When toggling a value on the screen, the output directly energizes according to the selected value.
3. You can override any output if you bypass the Bacnet array (1 - 16).
4. It is not possible to modify the set Bacnet array values.
5. After any output state gets modied, all overrides get cancelled after 1 minute of button inactivity, or if you scroll from one screen
to another screen.
CASE A: screen 2/2 display is dependent on Control type conguration. If mode is set to On/Off, binary options show.
CASE B: screen 2/2 display is dependent on Control type conguration. If mode is set to Analog, analog options show.
UO10 analog
0.0 Vdc
0.0 Vdc
UO11 analog
2/2 Test outputs