VT8600 SeriesUser Interface Guide
2/2 Setpoints
Max. heating
Min. deadband
Default heat
1.5 °C
32.0 °C
12.0 °C
13.0 °C
22.0 °C
Min. cooling
Supply air SP
50 %RH
Dehum. SP
SETPOINT SETTINGS 2/2
SETPOINT PARAMETER DETAILS
Conguration parameters default value Signicance and adjustments
Default heat
Default value: 22.0 °C (73 °F)
Default Heat
Used for hospitality applications in stand-alone mode only. When
devices are in deep unoccupied mode, any movement detected by
PIR resets actual occupied set points to fresh room default setting.
Default setpoint is used to write to Heating setpoint when
thermostat goes to Unoccupied mode.
Cooling setpoint is set according to Min. deadband; 18.0 to 26.5
°C (65 to 80 °F).
Parameter is only used when Stand-by mode = Rel.
Min. deadband
Default value: 1.5 °C (3 °F)
Minimum Deadband
Minimum deadband value between heating and cooling setpoints
applied only when any setpoints are modied.
Range: 1.0 to 2.5 °C, 0.5 °C increments (2, 3, 4 or 5 °F, 1.0 °F
increments).
Max heating
Default value: 32 °C (90 °F)
Maximum Heating
Maximum occupied and unoccupied heating setpoint adjustment.
Range: 4.5 to 32.0 °C (40 to 90 °F).
Min. cooling
Default value: 12.0 °C (54 °F)
Minimum Cooling
Minimum occupied and unoccupied cooling setpoint adjustment.
Range: 12.0 to 37.5 °C (54 to 100 °F).
Supply air SP
Default value: 13.0 °C (55 °F)
Free cooling supply air setpoint when economizer mode is
enabled.
50 to 90 °F (10.0 to 32.0 °C)
Dehum. SP
Default value: 50% RH
Dehumidification Setpoint
Used only if dehumidification sequence is enabled:
Range is: 30-95% RH (models with humidity sensor only).
Parameter only displayed on
models with built in humidity
sensor.