User Guide
VT8600 Series
31
User Interface Guide
© 2014 Viconics Technologies. All rights reserved.
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-01 www.viconics.com April 2
Schedule menu
9/10 Configuration
User password
Main password
0
0
Calib. temp.
0.0 °C
Calib. OS temp.
0.0 °C
Calib. humid.
0.0 %RH
Enabled
CONFIGURATION PARAMETERS SCREEN 9/10
PARAMETER DETAILS SCREEN 9/10
Conguration parameters default value Signicance and adjustments
Main password
Default value: 0
Main Password
Installer password. This parameter sets a protective access
password to prevent unauthorized access to conguration menu
parameters.
Default value of 0 does not prompt a password or lock access
conguration menu.
Range: 0 - 9999.
User Password
Default value: 0
User Password
User password. This parameter sets a protective access
password to prevent user unauthorized access to main screen
adjustments.
Default value of 0 does not prompt a password.
Range: 0 - 9999.
Schedule menu
Default value: Enabled
Toggles activation of schedule menu direct access
Enabled The Schedule Menu is directly accessible from the
main screen via a touch in the upper corner (see page 4).
Disabled The Schedule Menu can only be accessed through the
Setup Menu screens
Calib. temp.
Default value: 0.0 °C or °F
Calibration Temperature
Room temperature sensor calibration. Offset can be added or
subtracted to actual displayed room temperature.
Range: ± 2.5 °C, 0.5 °C increments (± 5.0 °F, 1.0 °F
increments).
Calib. OS temp.
Default value: 0.0 °C or °F
Calibration Outside Temperature
Outside air temperature sensor calibration. Offset that can be
added/subtracted to the actual displayed outdoor temperature.
Range: ± 2.5 °C, 0.5 °C increments (± 5.0 °F, 1.0 °F
increments).
These parameters are only displayed on
models with built in humidity sensor