VT8600 SeriesUser Interface Guide
PARAMETER DETAILS SCREEN 7/10
Conguration parameters default value Signicance and adjustments
Min fresh air
Minimum Fresh Air Value
Default value: 0 CFM
Minimum fresh air required. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max FA values (if
FA Range is set to other than 0 CFM). See Fresh Air Damper
Position section for more details.
0 to 20 000 CFM (0 to 9438 l/s, the value set cannot exceed
the value of FA Range parameter), 1 = increments
Max fresh air
Maximum Fresh Air Value
Default value: 0 CFM
Maximum fresh air allowed. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max FA values set
(if FA Range is set to other than 0 CFM). See Fresh Air Damper
Position section for more details.
0 to 20 000 CFM (0 to 9438 l/s, the value set cannot exceed
the value of FA Range parameter), 1 = increments
Min CO2
Minimum CO2 Level
Default value: 800 ppm
Minimum CO2 Level required. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max Pos values
set. See Fresh Air Damper Position section for more details.
0 to 2000 ppm, 10 ppm increments
Max CO2
Maximum CO2 Level
Default value: 1200 ppm
Maximum CO2 Level allowed. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max Pos values
set. See Fresh Air Damper Position section for more details.
0 to 2000 ppm, 10 ppm increments