User Guide

VT8600 Series
27
User Interface Guide
© 2014 Viconics Technologies. All rights reserved.
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-01 www.viconics.com April 2
7/10 Configuration
Min fresh air
Econo min pos
0 %
Max CO2
Min CO2
Max fresh air
100 %
800 ppm
0 l/s
Econo max pos
0 l/s
1200 ppm
CONFIGURATION PARAMETERS SCREEN 7/10
PARAMETER DETAILS SCREEN 7/10
Conguration parameters default value Signicance and adjustments
Econo min pos
Minimum Fresh Air Damper/Economizer Position
Default value: 0%
Minimum fresh air damper position. Effective only in Occupied
mode (Fan is ON). This value is also used to determine the fresh
air damper position based on the Min/Max CO2 and Min/Max
Pos values set. See Fresh Air Damper Position section for more
details.
0% to 100%, +/- 1% increments
Econo max pos
Maximum Fresh Air Damper/Economizer Position
Default value: 100%
Maximum fresh air damper position. Effective only in Occupied
mode (Fan is ON). This value is used to determine the fresh air
damper position based on the Min/Max CO2 and Min/Max Pos
values set. See Fresh Air Damper Position section for more
details.
0% to 100%, +/- 1% increments
Note: Viconics RTU HP IAQ Room Controller products and documentation for air damper position and output is based on 0-10 VDC
analog actuators. Many installations utilize 2-10 VDC actuators, which cannot be switched to 0-10 VDC control logic. The following
chart indicates the appropriate equivalent damper positions for use with 2-10 Vdc actuators.
Outside air percentage 0% 5% 10% 15% 20% 25% 30% 35% 40% 45% 50%
Setting for 0-10 Vdc Actuator 0% 5% 10% 15% 20% 25% 30% 35% 40% 45% 50%
Setting for 2-10 Vdc Actuator 20% 24% 28% 32% 36% 40% 44% 48% 52% 56% 60%
Outside air percentage 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
Setting for 0-10 Vdc Actuator 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
Setting for 2-10 Vdc Actuator 64% 68% 72% 76% 80% 84% 88% 92% 96% 100%