PARAMETER DETAILS SCREEN 5/10
Conguration parameters default value Signicance and adjustments
Heat stages
Number of heating stages.
Applicable to 2 stage models only
Default value: 2 stages
Will revert the operation of 2 stages Terminal Equipment Controller to single
stage operation only when the second heating step is not needed.
1 or 2 stages
Cool stages
Number of cooling stages
Default value: 2 stages
Will revert the operation of 2 stage Terminal Equipment Controller to single
stage operation only when the second cooling step is not needed.
1 or 2 stages
Econo. cong
Economizer conguration
Default value: Off
Controls the activity of the economizer functionality
On Economizer is activated
Off Economizer is deactivated
Changeover SP
Changeover setpoint
Default value: 55 °F (13.0 °C)
In Cooling mode.
The outside air temperature value at which the cooling will be switched over
from mechanical (compressor) to free cooling (economizer)
14 to 70 °F (-10.0 to 21.0 °C)
Mech. cooling
Mechanical cooling allowed
Default value: Off
In Cooling mode.
Allows the operation of the mechanical cooling if the free cooling (economiz-
er) cannot maintain the cooling setpoint.
Off Typically applies when the MS (mixed air temperature sensor) is installed
after the mechanical cooling refrigeration coils. In this case, mechanical
cooling will never operate at the same time as free cooling.
On Typically applies when the MS (mixed air temperature sensor) is installed
before the mechanical cooling refrigeration coils in the mixing plenum. In
this case, mechanical cooling is allowed when the free cooling (economizer
operation) cannot maintain the cooling setpoint.
Off or On