VT8600 SeriesUser Interface Guide
5/10 Configuration
Heat stages
Prop. band
2
3.0
Econo. config
Off
Changeover SP
13.0 °C
Cool stages
2
Mech. cooling
Off
CONFIGURATION PARAMETERS SCREEN 5/10
PARAMETER DETAILS SCREEN 5/10
Conguration parameters default value Signicance and adjustments
Prop. band
Default value: 3.0
Proportional Band Setting
Adjusts proportional band used by the Terminal Equipment Controller PI control
loop.
Note: default value of 3.0 gives satisfactory operation in most normal installation
cases. The use of a superior proportional band different than the factory one is
normally warranted in applications where Terminal Equipment Controller location
is problematic and leads to unwanted cycling of the unit. A typical example is
a wall mounted unit where Terminal Equipment Controller is installed between
return and supply air feeds and is directly inuenced by the supply air stream of
unit.
Value Effective Proportional Band
Fahrenheit Celsius
3 3 1.2
4 4 1.7
5 5 2.2
6 6 2.8
7 7 3.3
8 8 3.9
9 9 5.0
10 10 5.6