VT8600 SeriesUser Interface Guide
5/10 Configuration
Heat stages
Prop. band
2
3.0
Econo. config
Off
Changeover SP
13.0 °C
Cool stages
2
Mech. cooling
Off
CONFIGURATION PARAMETERS SCREEN 5/10
PARAMETER DETAILS SCREEN 5/10
Conguration parameters default value Signicance and adjustments
Prop. band
Default value: 3.0
Proportional Band Setting
Adjusts proportional band used by the Terminal Equipment Controller PI control
loop.
Note: default value of 3.0 gives satisfactory operation in most normal installation
cases. The use of a superior proportional band different than the factory one is
normally warranted in applications where Terminal Equipment Controller location
is problematic and leads to unwanted cycling of the unit. A typical example is
a wall mounted unit where Terminal Equipment Controller is installed between
return and supply air feeds and is directly inuenced by the supply air stream of
unit.
Value Effective Proportional Band
Fahrenheit Celsius
3 3 1.2
4 4 1.7
5 5 2.2
6 6 2.8
7 7 3.3
8 8 3.9
9 9 5.0
10 10 5.6