PARAMETER DETAILS SCREEN 4/10
Conguration parameters default value Signicance and adjustments
BO1 aux cong
Default value: NO
Binary Output Terminal
Output directly follows occupancy of the Terminal Equipment
Controller.
1) NO: Occ or St-By = Contact Closed / Unoccupied = Contact
Opened
2) NC: Occ or St-By = Contact Opened / Unoccupied = Contact
Closed. Output to follow directly main occupancy and Fan on
command.
Anti short cycle
Minimum On-Off operation time for stages
Default value: 2 minutes
Minimum On-Off operation time of cooling & heating stages.
IMPORTANT, anti-short cycling can be set to 0 minutes for
equipment that posses their own anti cycling timer. Do not use this
value unless the equipment is equipped with such internal timer.
Failure to do so can damage the equipment.
0, 1, 2, 3, 4 & 5 minutes
Min. sup. heat
Only valid if HT Type is set to Analog
Minimum supply heat temperature setpoint
Default value: 18.0 °C (64 °F)
Sets the minimum supply heat to be maintained by the
controller during occupied periods (Occupied or Temporary
Override).
From 50 °F up to 72 °F (10 °C up to 22 °C)
(increments: 0.5° or 5°)