User Guide

22
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-01 www.viconics.com April 2015
© 2015 Viconics Technologies. All rights reserved.
VT8600 SeriesUser Interface Guide
4/10 Configuration
Frost protec.
Heating CPH
Cooling CPH
Off
4
4
BO1 aux. config
NO
Anti short cycle
2 min
18.0 °C
Min sup. heat
CONFIGURATION PARAMETERS SCREEN 4/10
PARAMETER DETAILS SCREEN 4/10
Conguration parameters default value Signicance and adjustments
Cooling CPH
Cooling stages cycles per hour.
Default value: 4 CPH
Sets the maximum number of cooling stage cycles per hour
under normal control operation. It represents the maximum
number of cycles that the equipment will turned on and off in one
hour.
Note that a higher CPH will represent a higher accuracy of
control at the expense of wearing mechanical components faster.
3 or 4 CPH
For multi stage models, cool CPH applies to Y1 & Y2
Heating CPH
Heating stages cycles per hour.
Default value: 4 CPH
Will set the maximum number of heating stage cycles per hour
under normal control operation. It represents the maximum
number of cycles that the equipment will turn ON and OFF in one
hour.
Note that a higher CPH will represent a higher accuracy of
control at the expense of wearing mechanical components faster.
3, 4, 5, 6,7 & 8 CPH
For multi stage models, heat cph applies to W1 & W2
Frost protec
Frost protection enabled
Default value: Off
Off: no room frost protection
On: room frost protection enabled in all system mode at: 42 °F
( 5.6 °C )
Frost protection is enabled even in system Off mode
Off or On