CONFIGURATION PARAMETERS SCREEN 3/10
PARAMETER DETAILS SCREEN 3/10
Conguration parameters default value Signicance and adjustments
Standby time
Default value: 0.5 hours
Standby Time
Time delay between the moment where the PIR cover detects
last movement in the area, and the time which the Terminal
Equipment Controller stand-by setpoints become active.
Range: 0.5 to 24.0 hours in 0.5 hours increments.
Unocc. time
Default value: 0.0 hours
Unoccupied Time
Time delay between the moment where the Terminal Equipment
Controller toggles to stand-by mode, and the time which the
Terminal Equipment Controller unoccupied mode and setpoints
become active.
Factory value 0.0 hours: Setting this parameter to its default
value of 0.0 hours disables the unoccupied timer. This prevents
the Terminal Equipment Controller from drifting from stand-by
mode to unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours in 0.5 hours increments.
Temp. occ. time
Default value: 2 hours
Temporary Occupancy Time
Temporary occupancy time with occupied mode setpoints when
override function is enabled.
When Terminal Equipment Controller is in unoccupied mode,
function is enabled with either the menu or UI2 congured as
remote override input.
Range: 0 - 24 hours.
3/10 Configuration
Temp. occ. time
Unocc. time
Standby time
2.0 hrs
0.0 hrs
0.5 hrs
Deh. lockout
Deh. hysteresis
Enabled
5 %RH
These parameters are only displayed on
models with built in humidity sensor