PARAMETER DETAILS SCREEN 2/10
Conguration parameters default value Signicance and adjustments
Standby diff.
Default value: 2 °C ( 3 °F )
Standby Difference
When Standby mode is Offset, standby setpoints are calculated as:
Standby cool = Cool setpoint + Standby diff.
Standby heat = Heat setpoint - Standby diff.
Adjustable from 0.5 a 2.5 °C ( 1 - 5 °F )
Power-up delay
Default value: 10 seconds
On initial power up of the Terminal Equipment Controller (each
time 24 Vac power supply is removed & re-applied) there is a delay
before any operation is authorized (fan, cooling or heating). This can
be used to sequence start up multiple units / Terminal Equipment
Controller in one location.
10 to 120 seconds
Occupancy src
Default value: Motion
Occupancy Source
Motion: occupancy status is received from a motion sensor.
Schedule: occupancy status is determined by the schedule.