VT8600 SeriesUser Interface Guide
2/10 Configuration
Fan delay
On
Off
Standy mode
Absolute
Standby diff.
2.0 °C
Fan cont. heat
Power-up delay
10 Sec.
Occupancy src
Motion
CONFIGURATION PARAMETERS SCREEN 2/10
PARAMETER DETAILS SCREEN 2/10
Conguration parameters default value Signicance and adjustments
Fan cont. heat
Fan control
Default value: On
Fan control in heating mode.
When selecting On; the Terminal Equipment Controller in all
cases will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating stages
(terminals W1 & W2) are solicited, will not be energized. The fan
in this case will be controlled by the equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave the fan
always on.
ON OR OFF
For multi stage models, fan control applies to W1 & W2
Fan delay
Default value: Off
Fan delay extends fan operation by 60 seconds after the call for
heating or cooling ends.
Valid only for Auto fan mode. On fan mode will leave the fan
always on.
Off or On
Standby mode
Default value: Absolute
Standby Mode
Choose which standby setpoints are used for control.
Absolute: Standby entered values are used for standby mode.
Offset: Occupied setpoints +/- Standby diff. used for standby
mode.