PARAMETER DETAILS SCREEN 1/10
Conguration parameters default value Signicance and adjustments
UI 17
Universal input no.2 conguration
Default value: None
Universal Input No. 2
None: No function will be associated with the input. Input can be
used for remote network monitoring.
Door Dry: This conguration is only functional if universal input
16 is set to Motion NO or Motion NC or an onboard PIR sensor is
used. With this sequence enabled, the occupancy is now dictated
through those 2 inputs. Any motion detected will set the zone to
occupied status. The zone will remain permanently in occupied
mode until the door contact switch opens momentarily. The
Terminal Equipment Controller will then go in stand-by mode. If
more movements are detected, the occupied mode will resume.
While the door is opened, any movements detected by the remote
PIR sensor or the onboard PIR sensor will be ignored. Use a
Normally Closed contact switching device.
Contact opened = Door opened
Contact closed = Door closed
Override: temporary occupancy remote override contact.
Filter: a lter alarm shows on the Terminal Equipment Controller
LCD screen when the input is energized.
Service: a service alarm shows on the Terminal Equipment
Controller LCD screen when input is energized.
UI 19
Universal input no.3 conguration
Default value: None
Universal Input No. 3
None: no function associated with input though input can be used
for remote network monitoring.
CO2: the 0-10VDC input value is used as a 0-2000ppm
CO2 level:
0 VDC = 0ppm
10VDC = 2000ppm
Prog recovery
Progressive recovery enabled
Default value: Off
Progressive recovery is automatically disabled if UI 16 and / or
UI 17 are congured remote NSB
Off = no progressive recovery
The occupied schedule time is the time at which the system will
restart.
On = progressive recovery active.
The occupied schedule time is the time at which the desired
occupied temperature will be attained. The controller will
automatically optimize the equipment start time.
In any case, the latest a system will restart is 10 minutes prior to
the occupied period time.
Setpoint func.
Local setpoint settings
Default value = Dual Stp
Set the local setpoint interface for the user
Dual SP (Dual Occupied Setpoints Adjustment)
Attach SP (Single Occupied Setpoint Adjustment)
Mode button
Default value: Normal
Mode button
Determines whether all HVAC functions are available to user
control.
Normal: All HVAC functions available based on current application
can be accessed through cycling Mode button functions
Off-Auto: Only Auto and Off settings are available by cycling the
Mode button.