BACNET NETWORK SETTINGS
BACnet network set-up screen shows when BACnet is detected in model. Select desired parameter and use up or down arrow to set
parameter to desired value.
1/2 BACnet network
Baud rate
Auto
Network units
SI
Network lang.
English
BACnet status
Offline
COM address
254
254 value sets BACnet
®
network Ofine. Choose differ-
ent value to activate Online
Imperial or
Metric units
Language setting
Baud rate
settings
Displays BACnet status,
Ofine or Online
PARAMETER DETAILS
Conguration parameters default value Signicance and adjustments
Comm address
Terminal Equipment Controller
networking address
Default value: 254
Range: 0 to 254
Communication Address
For BACnet
®
MS-TP models, the valid range is from 1 to 127.
Default value of 254 disables BACnet
®
communication for the Terminal
Equipment Controller.
Network units
Default value: Imperial
Measurement Units
(Imperial): network units shown as Imperial units.
(SI): network units shown as International Metric units.
Network lang
Default value: English
EN, FR, SP for BACnet models only
Language Settings
Choices: English, French, Spanish, Chinese, Russian, Arabic, Bulgar-
ian, Czech, Danish, Dutch, Finnish, German, Hungarian, Indonesian,
Italian, Norwegian, Polish, Portuguese, Slovak, Swedish, Turkish
Baud rate
Default value: Auto
Baud Rate
(Auto): automatically detects BACnet
®
MS/TP baud rate.
Other choices: (115200, 76800, 57600, 38400, 19200, and 9600).
Leave the value at auto unless instructed otherwise.