BACNET NETWORK SETTINGS
BACnet network set-up screen shows when BACnet is detected in model. Select desired parameter and use up or down arrow to set
parameter to desired value.
1/2 BACnet network
Baud rate
Auto
Network units
SI
Network lang.
English
BACnet status
Offline
COM address
254
254 value sets BACnet
®
network Ofine. Choose differ-
ent value to activate Online
Imperial or
Metric units
Language setting
Baud rate
settings
Displays BACnet status,
Ofine or Online
PARAMETER DETAILS
Conguration parameters default value Signicance and adjustments
Comm address
Terminal Equipment Controller
networking address
Default value: 254
Range: 0 to 254
Communication Address
For BACnet
®
MS-TP models, the valid range is from 1 to 127.
Default value of 254 disables BACnet
®
communication for the Terminal
Equipment Controller.
Network units
Default value: Imperial
Measurement Units
(Imperial): network units shown as Imperial units.
(SI): network units shown as International Metric units.
Network lang
Default value: English
EN, FR, SP for BACnet models only
Language Settings
Choices: English, French, Spanish, Chinese, Russian, Arabic, Bulgar-
ian, Czech, Danish, Dutch, Finnish, German, Hungarian, Indonesian,
Italian, Norwegian, Polish, Portuguese, Slovak, Swedish, Turkish
Baud rate
Default value: Auto
Baud Rate
(Auto): automatically detects BACnet
®
MS/TP baud rate.
Other choices: (115200, 76800, 57600, 38400, 19200, and 9600).
Leave the value at auto unless instructed otherwise.