Application Guide
© 2015 Viconcis Technologies. All rights reserved.
VT8600 Rooftop, Heat Pump and Indoor Air Quality Controller
APPENDIX B OPTIONAL NETWORK SET-UP
+
-
ref
+
-
ref
+
-
ref
BACnet
thermostat
1
BACnet
thermostat
2
BACnet
thermostat
3
Notes:
- Wiring should be daisy chained
- Respect polarity
- If using 2 conductors shielded wires, connect the shield
of each feed together on the back of the controller. ONLY
ground the shield at one location. DO NOT connect the
shield to the ref terminal.
APPENDIX C CONTROLLERS’ OCCUPANCY SEQUENCE OF OPERATION SCHEMATIC
Setpoints
Tim
e
Unoccupied cool
Occupied cool
Stand-by cool
72°F
76°F
80°F
Movement detected
-
Stand-by timer reset
Into Stand-by mode
-
Unoccupied timer reset
Stand-by
time
Unoccupied
time
Into Unoccupied
mode
Next movement
detected
70°F
62°F
U
noccupied heat
Occupied heat
Stand-by heat
72°F
66°F
70°F
Deadband
Deadband
Deadband
22°C
24.5°C
26.5°C
22°C
21°C 21°C
19°C
16.5°C
BACnet
®
communication
wiring
No communication wires required
Wireless Communication