Install Instructions

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x : (514 ) 321-4150
028-0450-00
www.viconics.com | sales@viconics.com November 2014
© 2014 Viconics TEchnologies. All rights reserved.
VT8000 Series
14
ZigBee Pairing Procedure
ADDITIONAL CONFIGURATION - WINDOW AND DOOR SENSORS
For window and door contact sensors, additional configuration is necessary for the Room Controller sequences to function appropriately.
1. Go to the first page of the Configuration settings in the Room Controller interface.
2. If a Zigbee wireless window contact sensor has been paired with the Room Controller, select UI16 and make sure the function is set
to Window.
3. If a ZigBee wireless door contact sensor has been paired with the Room Controller, select UI17 and make sure the function is set to
Door Dry.
Note that these functions are not interchangeable; only UI16 can enable the window contact sensor functions for the Room Controller, and
only UI17 can enable the door contact functions for the Room Controller.
1/7 Configuration
UI 19
UI 17
UI 16
None
Door Dry
Window
Occupancy src
Motion
Smart recovery
Off
Setpoint func.
Attach Stp