Install Instructions
VT8000 Series
11
ZigBee Pairing Procedure
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x : (514 ) 321-4150
028-0450-00
www.viconics.com | sales@viconics.com November 2014
© 2014 Viconics TEchnologies. All rights reserved.
ASSIGN DEVICE DATA POINTS
1. In the Object field of the Explorer tab, click ZigBee Room Controller Configuration.
2. Click on the checkboxes for any device data points that you want to monitor in Building Expert. A maximum of 50 data points can be
selected. Use the Search for text box to locate specific data points.
3. Click on Unassign all to clear all selected data points and restart.
4. In the COV field, select the checkbox for the Wireless Zone Battery and Wireless Zone Status for any Zones that you intend to
use to pair sensors (see next section) so that they will be updated automatically to the MPM whenever the Room Controller has a
change in the current values. This can take up to 20 COV data points.
5. Select the checkboxes for any other data set points you want to have updated to the MPM automatically whenever the Room
Controller has a change in current values, up to a maximum of 40 COV data points counting those used for ZigBee sensors in the
previous step.
For more information on which points to select and what they represent in terms of Room Controller functionality, refer to the VTR8300/
VT8300 Series BACnet Integration guide, or the VT8600 Series BACnet Integration guide.