Overview
This procedure shows you how to pair an VT8000 Series Room Controller with one of the following ZigBee Sensors:
• Ceiling Mounted Sensor
• Door/Window Mounted Sensor
• Motion Sensor
The ZigBee Sensors can be paired with a stand-alone Room Controller, or with a Room Controller as part of a network. However, when
pairing a ZigBee Sensor with a Room Controller on a network, the Room Controller must first be bound to a StruxureWare Lite
Multi-Purpose Manager.
You can pair up to 10 ZigBee Sensors per Room Controller. Each MPM can connect wirelessly with up to 30 ZigBee enabled devices
such as Room Controllers.
SETTINGS
You must correctly set the following parameters to successfully pair a ZigBee Sensor with a Room Controller:
• PAN ID to value less than 499 if Room Controller is to be bound to a MPM.
• PAN ID to value greater than or equal to 500 if the Room Controller is stand-alone.
• PAN ID parameter in Building Expert set to the same value as in the Room Controller.
• Permit join set to ON in Building Expert and Room Controller and then set to OFF in Building Expert and the Room Controller after a
successful pairing.
INSTALLATION STEPS
Perform the following steps to successfully pair the ZigBee Sensor to the Room Controller:
1. Bind the Room Controller to the MPM.
2. Set the parameters for the MPM.
3. Set Permit Join to On in the Room Controller and MPM
4. Pair the Sensor with the Room Controller
5. Install the Sensor at the selected location (see Installation Guide).