Pairing VT8000 Series Room Controllers with ZigBee Sensors Installation Guide and Procedure Commercial and Hotel/Lodging HVAC Fan Coil Applications
ZigBee Pairing Procedure VT8000 Series Quick setup The quick set-up assumes all back-end configurations of the stand alone Room Controller acting as coordinator or the Multi-Purpose Manager (MPM) coordinator for the ZigBee network have already been done. It also assumes the user is familiar with the Permit Join function and the Wireless Ecosystem screen functions. PROCEDURE 1. Set Permit Join on your Room Controller (or networked MPM coordinator if used) to On. 2.
ZigBee Pairing Procedure 3 VT8000 Series Overview This procedure shows you how to pair an VT8000 Series Room Controller with one of the following ZigBee Sensors: • Ceiling Mounted Sensor • Door/Window Mounted Sensor • Motion Sensor The ZigBee Sensors can be paired with a stand-alone Room Controller, or with a Room Controller as part of a network. However, when pairing a ZigBee Sensor with a Room Controller on a network, the Room Controller must first be bound to a StruxureWare Lite Multi-Purpose Manager.
ZigBee Pairing Procedure VT8000 Series Bind Room Controller to MPM This procedure shows you how to bind a Room Controller to a MPM using Building Expert. CONFIGURE VT8000 SERIES 1. In the center of the top of the screen, touch and hold this point for 3 seconds to enter setup mode. 2. Select Network. 3.
ZigBee Pairing Procedure 5 VT8000 Series LOGIN TO MPM Smart StruxureWare Building Expert requires an ESR version of Firefox. You can download it at: http://www.mozilla.org/en-US/firefox/organizations/all.html 1. Type the default address in the address bar (10.50.80.3 for MPM-GW and MPM-UN, 10.50.80.4 for MPM-VA). 2. Verify Building Expert login page shows. 3. Select Language (default English). 4. Enter User name (default ‘admin’). 5. Enter Password (default ‘admin’). 6. Click on Login.
ZigBee Pairing Procedure VT8000 Series Building Expert loads to the default page. CONFIGURE MANAGER In Building Expert, click Configuration tab. 2. In Controller Settings (CFG1), set Adjust Time, Save Period, Time Zone Offset, and Enable DST (if applicable). 3. Toggle Enable. 4. In Ethernet Settings (ETH1), set IP, Netmask, Gateway, DNS, and Email Source with the appropriate addresses for your network. 5. Click on Devices window, and select your MPM.
VT8000 Series 6. Click on the Edit Settings toggle. A warning message will appear, click on OK to continue. 7. Set Node Type as Coordinator or Router. 8. Set Channel to a value between 11 - 25 matching the channel value set on the Room Controller 9. Set PAN ID (dec) to a value matching the pan. ID value set on the Room Controller. 10. Set Stack Profile to 2 - ZigBee_Pro. 11. Set Security Profile to Home Automation 12. Click Save. Viconics Technologies Inc. 028-0450-00 | 9245 Langelier Blvd.
ZigBee Pairing Procedure VT8000 Series ADD DEVICE 1. In the Explorer tab of Building Expert, click the Add Device button. A new window opens. 2. Select the device you want to add. NOTE: The device model selected from the device list must be identical to the model number of your device. Click the Add Devices button. Building Expert automatically adds the device to your Room Controller. © 2014 Viconics TEchnologies. All rights reserved. 3. Viconics Technologies Inc.
ZigBee Pairing Procedure 9 VT8000 Series Set Parameters for MPM 1. In Devices pane, select the newly added device. 2. Navigate down the page to ZigBee Room Controller Configuration on the Explorer tab. Viconics Technologies Inc. 028-0450-00 | 9245 Langelier Blvd. | St.-Leonard | Quebec www.viconics.com | sales@viconics.com | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 November 2014 © 2014 Viconics TEchnologies. All rights reserved.
ZigBee Pairing Procedure VT8000 Series Click Bind. A new window opens and Building Expert searches for the Com Address and Extended Node ID for your device. 4. In the Select device window, select the device you want to bind with your MPM. 5. Click Bind device. Building Expert adds the device’s Extended Node ID and COM Address information to the selected Room Controller in the device list. © 2014 Viconics TEchnologies. All rights reserved. 3. Viconics Technologies Inc.
ZigBee Pairing Procedure 11 VT8000 Series 1. In the Object field of the Explorer tab, click ZigBee Room Controller Configuration. 2. Click on the checkboxes for any device data points that you want to monitor in Building Expert. A maximum of 50 data points can be selected. Use the Search for text box to locate specific data points. 3. Click on Unassign all to clear all selected data points and restart. 4.
ZigBee Pairing Procedure VT8000 Series Set Permit Join and Pair ZigBee Sensor(s) The following procedure assumes the Room Controller is either stand-alone or has already been bound to a MPM acting as a coordinator. See Appendix A for information on how to pair a ZigBee sensor with a Room Controller bound to a MPM in a network including multiple MPMs.
ZigBee Pairing Procedure 13 VT8000 Series PAIR ZIGBEE SENSOR(S) WITH ROOM CONTROLLER For a full description of how to install a ZigBee sensor, refer to the appropriate Installation Guide for the ZigBee sensor you are trying to pair with your Room Controller. Navigate to the Wireless Ecosystem screen on your Room Controller. 1. Go to the first Zone screen that is not already paired with a ZigBee sensor.
ZigBee Pairing Procedure VT8000 Series ADDITIONAL CONFIGURATION - WINDOW AND DOOR SENSORS For window and door contact sensors, additional configuration is necessary for the Room Controller sequences to function appropriately. 1. Go to the first page of the Configuration settings in the Room Controller interface. 2. If a Zigbee wireless window contact sensor has been paired with the Room Controller, select UI16 and make sure the function is set to Window. 3.
ZigBee Pairing Procedure 15 VT8000 Series DISABLING PERMIT JOIN 1. Once your ZigBee sensor has joined the network, verify that the last four digits of the IEEE address on the sensor match what shows on the Room Controller screen. More than one ZigBee sensor may have joined, so confirm that the correct type has joined for each zone that you use to pair a ZigBee sensor with the Room Controller.
ZigBee Pairing Procedure VT8000 Series Appendix A Binding ZigBee Sensors to Room Controllers in Network with Multiple MPMs When pairing a ZigBee sensor with a Room Controller that is part of a network that involves multiple MPMs, it is necessary for all of those MPMs to be networked using IP/Ethernet (UDP) or Canbus, and to be functioning as a coordinator for their local ZigBee network of Room Controllers.
ZigBee Pairing Procedure 17 VT8000 Series To use the ZigBee wireless sensors in a network with multiple MPMs, the general network architecture must resemble the diagram shown below. If the general design of your network installation with MPMs, Room Controllers and ZigBee sensors does not match that shown in the diagram below, please contact Support for more information. Note: Make sure that each MPM controlling a ZigBee network has a different PAN ID.