Install Instructions

VT8000 Series
15
ZigBee Pairing Procedure
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x : (514 ) 321-4150
028-0450-00
www.viconics.com | sales@viconics.com November 2014
© 2014 Viconics TEchnologies. All rights reserved.
DISABLING PERMIT JOIN
1. Once your ZigBee sensor has joined the network, verify that the last four digits of the IEEE address on the sensor match what shows
on the Room Controller screen. More than one ZigBee sensor may have joined, so confirm that the correct type has joined for each
zone that you use to pair a ZigBee sensor with the Room Controller.
2. Once the sensor has been paired with the Room Controller, change the Set function to parameter to match the correct type of
ZigBee sensor. The options are:
None
Default setting, no sensor function specified.
Door
Default behaviour is that if the door is opened, then closed, and the room controller does not detect motion for 15
seconds, then the Room Controller will switch to Standby setpoints.
Window
Default behaviour is that triggering the sensor turns off the HVAC air compressor.
Motion
Default behaviour is that triggering the sensor will switch the Room Controller to Occupied setpoints.
Status
Use this setting to monitor the functioning of the sensor without allowing it to affect the Room Controller’s settings.
Remove
Select this setting to clear the sensor settings from this Zone.
if the incorrect function is configured, then either the Paired status will change to Invalid (when incorrectly setting
motion<-->contact), or incorrect responses will be triggered in the Room Controller (example window<-->door); i.e. the room
controller can tell the difference between a contact sensor and a motion sensor, but it needs to be told if the contact is a window
sensor or door sensor.
3. After you have confirmed that you have successfully joined all the ZigBee sensors you need with your Room Controller, set the Permit
Join setting on both the Room Controller and Building Expert to Off. This will prevent any other ZigBee sensors from accidentally
joining your network.
Once the pairing procedure is complete, proceed with the physical installation of your ZigBee sensor(s) according to the instructions in the
Installation Guide appropriate to the model(s) of ZigBee sensor(s) you are using.
Set function to
Status
1/10 Zone
Battery
Yes
Paired
0xEB6B
IEEE address
None
None
Normal
Permit join
On