Submittal Sheet
Specifications
Thermostat power requirements: 19-30 Vac 50 or 60 Hz; 2 VA ( RC & C ) Class 2
RC to RH jumper 2.0 Amps 48 VA maximum
Operating conditions: 0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Storage conditions: -30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Sensor: Local 10 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control accuracy: ± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated
Occupied and unoccupied setpoint range
cooling:
12.0 to 37.5 °C ( 54 to 100 °F )
Occupied and unoccupied setpoint range
heating:
4.5 °C to 32 °C ( 40 °F to 90 °F )
Room and outdoor air temperature range -40 °C to 50 °C ( -40 °F to 122 °F )
Proportional band for room temperature control: Factory set, heating and cooling at: 1.1°C ( 2.0°F )
Digital inputs: Relay dry contact only across C terminal to DI1 or DI2
Contact output rating: Each relay output: ( Y1, Y2, G, W1, W2 & AU )
30 Vac, 1 Amp. maximum
30 Vac, 3 Amp. in-rush
Economizer analog output rating:
0 to 10 Vdc into 2KΩ resistance min.
Economizer analog output accuracy: ± 3% typical
Wire gauge 18 gauge maximum, 22 gauge recommended
Dimensions: 4.94” x 3.38” x 1.13”
Approximate shipping weight: 0.75 lb ( 0.34 kg )
Agency Approvals all models:
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada), File
E27734 with CCN XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada)
Agency Approvals all models
FCC: Compliant to CFR 47, Part 15, Subpart B, Class A
(US)
CE: EMC Directive 89/336/EEC (Europe Union)
C-Tick: AS/NZS CISPR 22 Compliant (Australia / New
Zealand) Supplier Code Number N10696
Agency Approvals Wireless models
FCC: Compliant to: Part 15, Subpart C
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE
FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND
(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.
Drawing & dimensions
Fig.1 – Thermostat dimensions
Important notice
All VT7600 series controls are
for use as operating controls
only and are not safety devices.
These instruments have
undergone rigorous tests and verifications
prior to shipment to ensure proper and reliable
operation in the field. Whenever a control
failure could lead to personal injury and/or
loss of property, it becomes the responsibility
of the user / installer / electrical system
designer to incorporate safety devices (
such as relays, flow switch, thermal
protections, etc…) and/or alarm system to
protect the entire system against such
catastrophic failures. Tampering of the
devices or miss application of the device will
void warranty.