Before Starting Pairing Procedure
Verify the following parameters on the SER8300 controller are set correctly to
avoid failure.
PAN ID
Personal Area
Network Identification
Defaultvalue=0
Range: 0 -1000
This parameter only appears when a wireless network adapter is
present. If the Terminal Equipment Controller is installed as a stand-
alone unit or with a BACnet™ or Echelon™ adapter, this parameter is
not used or displayed.
The default value of 0 is not a valid PAN ID.
The valid range of available PAN ID is from 1 - 1000.
Range 1 - 500 is for centralized networked applications using a MPM.
Range 501 - 1000 is for stand-alone applications where no MPM with
wireless stat driver is used.
Channel
Channel selection
Defaultvalue=10
Range: 10 - 26
This parameter only appears when a wireless network adapter is
present. If the Terminal Equipment Controller is installed as a stand-
alone unit or with a BACnet™ or Echelon™ adapter, this parameter is
not used or displayed.
Schneider-Electric recommends using only channels 15 and 25 only.
The default value of 10 is not a valid channel. The valid range of
available channel is from 11 to 26.