User's Manual
SED - WIN and SED - DOR
4
Wireless Door/Window Switch
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 http://www.schneider-electric.com/buildings
II-SE8000-SEDWINDOR-US.EN.10.2013.v1 October 2013
© 2013 Schneider Electric. All rights reserved.
Pairing Process Procedure
NOTE: See SER/SE installation manual for details on PAN ID parameter.
PAN ID for Centralized Networked Applications with MPM
SER8300 Series SE 72 / 73 Series*
1 - 500 1 - 250
PAN ID for Stand-alone Applications with no MPM
SER8300 Series SE 72 / 73 Series*
501 - 1000 251 - 500
Note: SE7000 Room Controllers are only compatible if a network with a Coordinator is
present.
Configuring Actions
Short Switch Duration Result
Approximately 1 second Enter Pairing Mode (page 8)
Approximately 1 second (after being paired) Displays MAC address (page 8)
4+ seconds and less than 10 seconds Battery Status (page 13 )
10+ seconds and less than 20 seconds Diagnostic Mode (page 12)
20+ seconds Resets Switch
Using SER8300 Controllers for Stand-alone Systems
When PAN ID is used with Range of 501 - 1000 for Stand-Alone Systems
In this application, the SER8300 controller(s) are the coordinators to their own
systems and are network masters for each wireless switch reporting to them. A
unique network is needed for proper functionality according to the following:
•WirelesscontrollerfactorydefaultChannelandPANID=controller(s)ofine.
•EachSER8300controllerisitsownnetworkcoordinator.
•RangeofPANIDonallcontrollerstouseis501-1000.Thisrangeisreserved
for stand-alone system operation.
Notes:
• Each SER8300 Controller uses a unique PAN ID and/or Channel settings.
• If all available PAN ID’s are used (501-1000), use a different channel.
• Up to 20 switches can be linked to each SER8300 Controller.