User's Manual

2
Troubleshooting instructions
Viconics Line Voltage FCU, wireless Door / Window switched association:
1. Set “Pan ID” = 1-499 (networked thermostat) or 501 and up (for stand-alone thermostats)
2. Set “Channel” parameter to: 25 (recommended)
3. Mac = 1 and up (unique per stat)
4. Set configuration parameter of “BI1” & “BI2” to “NONE”.
5. Reset the configuration of “BI1” to “Window” and/or “BI2” to “DoorDry”
6. (OPTIONAL) To reset the Wireless Switch to its factory default settings, simply jump the switch (use a metal ball pen) & hold
for 20+ seconds.
7. (IMPORTANT NOTE) When you are able to view 5 fast blinks, this indicates that you have successfully set the parameters
to their default settings.
8. Do the following to both Door & Window switches. Jump once: Scan mode active (Indicated by 2 slow blinks)
9. Hold close to the stat, on the side, where the stat com module is located.
10. You will get several flashes that correspond to your MAC address. (I.e. MAC=43) The Switch will illuminate 4 short blinks
followed by another 3 short blinks. The switch or switch(es) is/are now associated.
Demo Operation:
1. Using the keypad, call for heat or cool on the stat (Apply a minimal amount for testing purposes only). This will verify that the
“Occ” set point is active.
2. Close both switches on the table.
3. If you open the window switch: The “Heat” or “cool” function (the one enabled) will shut down (disabled) when the window is
opened. Also, if you close the window: “Heat” or “cool” function will resume.
4. If you close the door switch (the switch should already be closed at this point), cover the PIR with any object or colored
adhesive tape. Open & Close the door switch once. Wait 10 seconds
. (The stat will go in “stand-by” mode). You will see the
“heat” or “cool” demand shut-off & you will have the “stand-by” prompt you on the display.
5. Uncover the PIR sensor. The stat will detect a movement (while the door is still closed). Stat will resume its function in
“occupied” mode according to the “heat” or “cool” demand.
Internal View
The additional following documents are available at: www.viconics.com
Information on installation & commissioning of the VWA5000W wireless switches on document LIT-VWA5000W-Exx
Information on installation of the Terminal Equipment Controller (VTR7300), is available on document LIT-VTR7300-PIR-Exx
PIR Hospitality application information and examples, are available on document: APP-HOSPITALITY-PIR-VTR73-Guide-Exx
HVAC Fan Coil application information and examples, are available on document: APP-VTR7300-PIR-Exx
Information on the Wireless models (VTR3xxX5x00W), is available on documents: ITG-VWG-40-BAC-Exx and MAN Wireless Stat
Driver Guide-Exx
Hidden service LED
Hidden switch