User's Manual
5
VTR73xxA Terminal Equipment Controller Terminal Identification and Function
Terminal Identification All VTR73xxA5x00(X) Terminal Equipment Controller
Terminal 3 Tx – Rx Communication
Terminal 4 Power Hot 7.0 Vdc
Terminal 5 Power Common
Terminal 13 BI 1 ( Configurable )
Terminal 14 Scom
Terminal 15 BI 2 ( Configurable )
VTR73xxA Terminal Equipment Controller Power & Communication Wiring to VC3xxxX Relay Pack
3 - Tx / Rx
4 - 7 Vdc Power Hot
5 - Power Common
To other VC3xxxX
Relay Pack
VC3504E
Relay Pack
VC3300E
Relay Pack
VTR73xxA
Terminal Controller
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
Only ONE VC3xxxX Relay Pack with remote monitoring inputs can be used under a single VTR73xxA Controller. All other slave units
must me either VC3xxxX Relay Pack(s) WITHOUT remote inputs. A maximum of 10 VC3xxxX Relay Packs can be used for a single
VTR73xxA Terminal Equipment Controller.
From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack
o Existing or new field wires
o 3 minimum required 14-22 Ga Solid or Stranded. Shield not necessary.
From the first VC3xxxX Relay Pack connected to the controller to all other VC3xxxX Relay Pack(s)
o Existing or new field wires
o 2 minimum required 14-22 Ga Solid or Stranded. Shield not necessary.
o Connect only 1 Power Common & 2 Tx-Rx Communication
The VTR7300 to VC3000 Transformer Relay Pack can use ANY network wiring topology as either required, being more
practical or based on availability and topology of existing wires.
Wiring of Local Inputs to VTR73xxA Terminal Equipment Controller
V
TR73xxA
Terminal Controller
13 - BI 1
14 - Scom
15 - BI 2
Local BI 1 Input by configuration:
- None ( monitoring only
- Remote motion detector: Motion NO or Motion
C
- Remote Night Setback:
- Window contact: Window
Local BI 2 Input by configuration:
- None ( m onito ri ng only
)
- Door contact: DoorDry
Dais
y
Chained To
p
olo
gy
Sta
r
To
p
olo
gy
Mixed Daisy Chained &
Start Topology