VT7682S5000W Wireless Central Manager Installation Guide For Commercial HVAC Applications th December 4 2012 / 028-0366-R1 CONTENTS Installation Location Installation Features overview Model Number Terminal, Identification and Function Wiring Screw terminal arrangement Configuring and Status Display Instructions Status display User Interface User configuring instructions menu Local keypad interface Occupied setpoints adjustments Installer Configuration Parameter Menu Troubleshooting guide All models Speci
I NSTALLATION Remove the security screw on the bottom of Terminal Equipment Controller cover. Open unit by pulling on the bottom side of Terminal Equipment Controller (fig. 1). Remove wiring terminals from sticker. Please read the FCC ID and IC label installed in the cover upon removal of cover for the wireless products. Location 1. Should not be installed on an outside wall. 2. Must be installed away from any direct heat source. 3. Should not be installed near an air discharge grill. 4.
10. Insert each wire according to wiring diagram. 11. Gently push excess wiring back into hole (fig. 3). 12. Re-Install wiring terminals in their correct locations (fig. 3). 13. Re-install the cover (top side first) and gently push extra wire length back into the hole in the wall. 14. Install security screw. When replacing an existing Terminal Equipment Controller, label the wires before removal of the Terminal Equipment Controller. Electronic controls are static sensitive devices.
MODEL NUMBER Part number Description VT7682S5000W Wireless Central Manager TERMINAL , IDENTIFICATION AND FUNCTION Wiring Terminal Use Terminal Identification Description 4 – RC 24Vac hot 24 V ~ Hot Power supply of controller (hot side) 5 – C 24Vac com 0 V ~ Com Power supply of controller (com side) 14 – Scom Scom Reference input for OS OS Outside air temperature sensor input 15 – OS 4 | VT7682S Series-Installation Guide
Screw terminal arrangement Left top connector 24 V ~ Hot 0 V ~ Com Bottom connector Scom OS Outdoor sensor accessories MODEL NO. S2020E1000 DESCRIPTION Outdoor temperature sensor (NEMA 4 Enclosure) S1010E1000 Outdoor temperature sensor Outdoor temperature sensors use 10K NTC thermistor. S2020E1000 S1010E1000 Temperature vs. resistance chart for 10 Kohm NTC thermistor ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm -40 -40 324.3197 -20 -4 94.5149 0 32 32.1910 20 68 12.
User menu flow chart: NOTE: Prompts may not all be present depending on model selected If status is: Unoccupied MENU Override schd Y/N If status is: Temporary Occupied Time, Temperat set? Y/N Sys mode set? Y/N Cancel ovrd Y/N Clock set? Y/N Schedule set? Y/N Exit menu Y/N off heat cool auto Time set? Y/N Cooling set? Y/N Temperature Heating set? Y/N 12/24hrs set? Y/N Time Day °F/°C set? Y/N Exit? Y/N Exit? Y/N 12 / 24 °C °F Temperature Exit? Y/N Day set? Y/N Sunday set? Y/N Satur
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS Status display The Terminal Equipment Controller features a two-line, eight-character display. There is a low level backlight that is always active and can only be seen at night. When left unattended, the Terminal Equipment Controller has an auto scrolling display that shows the current status of the system. Each item is scrolled sequentially with the back lighting in low level mode. Pressing any key will cause the back light to come on to high level.
If alarms are detected, they will automatically be displayed at the end of the status display scroll. During an alarm message display, the back lit screen will light up at the same time as the message and shut off during the rest of the status display. Two alarms maximum can appear at any given time. The range of zones that can be in alarm is 1 to 253.
When left unattended for 45 seconds, the display will resume automatic status display scrolling. To turn on the back light, press any key on the front panel.
C) Temperature setpoints Temperat set Y/N This menu permits the adjustment of occupied temperature setpoints as well as the desired temperature units (°F or °C). Setpoints are written to RAM and EEPROM. Cooling setpoint Occupied mode Heating setpoint Occupied mode Cooling No next Heating No next set? Y/N Yes down set? Y/N Yes down Use ▲▼ keys to set value, Yes key to confirm Cooling Use ▲▼ Heating Use ▲▼ 70.0 °F To set value 68.
Occupied Day? Y/N No next Yes down Occupied 00:00 AM Unoccup 00:00 AM No next No next Yes = Daily schedules will be Occupied Yes down Yes down accessed Day? Y/N No = Unoccupied mode all day Yes key to access day scheduling, No key to jump to next day Yes = Will copy previous day Yes next Yes next Copy Y/N Copy Y/N schedule Previous Previous No = Daily schedules will be No down No down accessed Yes key to copy previous day, No key to set new time value for each day Use ▲▼ Use ▲▼ Use ▲
Ex. #2 Commercial building which is occupied all weekend Event Setpoint Monday Tuesday Wednesday Thursday Friday Saturday Sunday Period #1 - Event #1 Occupied Cool Heat 72 °F 70 °F 8.00 AM 8.00 AM 8.00 AM 8.00 AM 8.00 AM 12.00 AM ** 12.00 AM ** Period #1 - Event #2 Unoccupied Cool Heat 80 °F 62 °F 5.00 PM 5.00 PM 5.00 PM 5.00 PM 5.00 PM 11.59 PM ** 11.
Ex. #1 Four event retail establishment schedule Monday Tuesday Wednesday Period 1 Event 1 Occupied Cool Heat 72°F 70°F 7.00 AM 7.00 AM 7.00 AM Period 1 Event 2 Unoccupied Cool Heat 80°F 62°F 5.00 PM 5.00 PM 5.00 PM Period 2 Event 3 Occupied Cool Heat 72°F 70 °F 12.00 PM * 12.00 PM * 12.00 PM * Period 2 Event 4 Unoccupied Cool Heat 80°F 62 °F 12.00 PM * 12.00 PM * 12.00 PM * Thursday 7.00 AM 5.00 PM 7.00 PM 10.30 PM Event Setpoint Friday 7.00 AM 5.00 PM 7.00 PM 10.30 PM Saturday Sunday 12.
H) Clock/Day Settings Clock set Y/N This section of the menu permits the user to set the time and day. Time setting Time set? Y/N Time 0:00 No next Yes down Use ▲▼ To set value Day setting Day set? Y/N Day Monday No next Yes down Use ▲▼ To set value Time format setting 12/24hrs set? Y/N 12/24hrs 12 hrs No = exit Yes down Use ▲▼ To set value I NSTALLER CONFIGURATION P ARAMETER MENU Configuration can be done through the network or locally at the Terminal Equipment Controller.
CONFIGURATION PARAMETERS DEFAULT VALUE PswrdSet Configuration parameters menu access password Default value = 0 No password prompted SIGNIFICANCE AND ADJUSTMENTS This parameter sets a password access to prevent unauthorized access to the configuration menu parameters. A default value of “0” will not prompt a password or lock the access to the configuration menu. Range is: 0 to 1000 Com Addr This parameter is used to set the MAC address.
lockout Keypad lockout levels 0 = No lock 1 = Low level Default value = 0 No lock 2 = Medium level 3 = High Level 0 1 2 3 ToccTime Temporary occupancy time Default value = 3 hours Permanent Hold Clock Setting Schedule Setting System Mode Setting Occupied Setpoints Resume/ Override scheduling LEVEL USER KEY FUNCTIONS Temporary occupancy time with occupied mode setpoints when override function is enabled When the Terminal Equipment Controller is in unoccupied mode, function is enabled with either th
TROUBLESHOOTING GUIDE All models Symptom No display on the Terminal Equipment Controller Keyboard menu does not access all functions Digital display shows missing digits or erratic segments Possible Cause Absent or incorrect supply voltage Overloaded power transformer Keyboard locked Defective display 17 | VT7682S Series-Installation Guide Corrective Action 1. Check power supply voltage between C & RC to be from 19-30 VAC 2.
S PECIFICATIONS Terminal Equipment Controller power requirements: Operating conditions: Storage conditions: Outdoor air Temperature sensor Wire gauge: Approximate shipping weight: Agency Approvals all models: Agency Approvals all models: Agency Approvals Wireless models: 19-30 VAC 50 or 60 Hz; 2 VA Class 2 0 °C to 50 °C ( 32 °F to 122 °F ) 0% to 95% R.H. non-condensing -30 °C to 50 °C ( -22 °F to 122 °F ) 0% to 95% R.H. non-condensing -40 °C to 50 °C ( -40 °F to 122 °F ) 18 gauge maximum, 22 gauge 0.
DRAWING & DIMENSIONS Viconics Technologies Inc. Tel.: 19 | VT7682S Series-Installation Guide Fax: Toll free: www.viconics.