- Numbers
- 1. (None): No function will be associated with the input
- 4. (Filter): a backlit flashing Filter alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied to a differential pressure switch that monitor filters
- 5. (Service): a backlit flashing Service alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
- 1. (None): No function will be associated with the input
- 2. (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold water change over switching in 2 pipe systems.
- Contact closed = Cold water present
- Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
- 3. (COC/NC) Change over dry contact. Normally Cool: Used for hot / cold water or air change over switching in 2 pipe systems.
- Contact closed = Hot water present
- Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
- 4. (COS) Change over analog sensor: Used for hot / cold water or air change over switching in 2 pipe systems.
- Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
- 5. (SS) Supply air sensor monitoring: Used for supply air temperature monitoring.
- Only used for network reporting of the supply air temperature. Has no internal function in the thermostat.
- Range is: 0 to 500
- This parameter (Personal Area Network Identification) is used to link specific thermostats to a single specific Viconics wireless gateway ( VWG ) For every thermostat reporting to a gateway ( maximum of 30 thermostats per gateway ), be sure you set the SAME PAN ID value both at the gateway and the thermostat(s).
- Range is: 10 to 26
- Viconics recommends using only the 2 last channels ( 25-2575MHz and 26-2580MHz )
- Range is: 0 to 254
- This parameter / function is not currently supported by the wireless thermostats.
- BI1
- Default value = None
- (None): No function will be associated with the input
- (Filter): a backlit flashing Filter alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied to a differential pressure switch that monitor filters
- (Service): a backlit flashing Service alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
- UI3
- Default value = None
- (None): No function will be associated with the input
- (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold water or air change over switching in 2 pipe systems.
- Contact closed = Cold water or air present
- Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
- (COC/NC) Change over dry contact. Normally Cool: Used for hot / cold water or air change over switching in 2 pipe systems.
- Contact closed = Hot water present
- Only used and valid if system is setup as 2 pipes. Parameter (Pipe No ) set as 2 pipes.
- (COS) Change over analog sensor: Used for hot / cold water or air change over switching in 2 pipe systems.
- Only used and valid if system is setup as 2 pipes. Parameter (Pipe No ) set as 2 pipes.
- (SS) Supply air sensor monitoring: Used for supply air temperature monitoring.
- 2.0 Pipes, will limit the number of sequences of operation available from 0 to 3
15
St-By CL
Stand-by cooling setpoint limit
Default value = 78 °F
The value of this parameter should reside between the occupied and unoccupied
cooling setpoints and make sure that the difference between the stand-by and
occupied value can be recovered in a timely fashion when movement is detected
in the zone.
Stand-by cooling setpoint range is: 54 to 100 °F ( 12.0 to 37.5 °C )
Unocc HT
Unoccupied heating setpoint
Default value = 62 °F
Unoccupied heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
Unocc CL
Unoccupied cooling setpoint limit
Default value = 80 °F
Unoccupied cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
heat max
Maximum heating setpoint limit
Default value = 90 °F ( 32 °C )
Maximum occupied & unoccupied heating setpoint adjustment.
Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
cool min
Minimum cooling setpoint limit
Default value = 54 °F ( 12 °C )
Minimum occupied & unoccupied cooling setpoint adjustment.
Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
Set Type
Temporary setpoint enable
Default is : Permnent
Enables temporary setpoints
feature to any change of
occupied or unoccupied setpoint.
Temporar: (temporary) Local changes to the heating or cooling setpoints by the
user are temporary. They will remain effective for the duration specified by
ToccTime. Setpoints will revert back to their default value after internal timer
ToccTime expires.
To change setpoints permanently, revert to No this variable or write setpoints
through the network. Any setpoints written through the network will be permanent
ones and saved to EEPROM.
Permnent: (permanent) Any change of occupied or unoccupied setpoints through
the keypad by the user are permanent and saved to & EEPROM
TOccTime
Temporary occupancy time
Default value = 2 hours
Temporary occupancy time with occupied mode setpoints when override function
is enabled
When the thermostat is in unoccupied mode, function is enabled with either the
menu or UI2 configured as remote override input.
Range is: 0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours
deadband
Minimum deadband
Default value = 2.0 °F ( 1.0 °C )
Minimum deadband value between the heating and cooling setpoints. If modified,
it will be applied only when any of the setpoints are modified.
Range is: 2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C, 0.5 °C increments )
cal RS
Room temperature sensor
calibration
Default value = 0.0 °F or °C
Offset that can be added/subtracted to actual displayed room temperature
Range is: ± 5.0 °F, 1.0 °F increments ( ± 2.5 °C, 0.5 °C increments )
cal RH
Humidity sensor calibration
Default value = 0 %RH
Offset that can be added/subtracted to actual displayed humidity by ± 15.0 %RH.
Range is : ± 15.0 %RH