User Manual

12
To View or Change the Fan Mode
To view the current fan mode setting:
1. TypeFM<enter>. The response will be
: fm
2(or 0, 1, or 3)
2indicatesthatthefanisinthedefaultmode2.
To changethefanmodesettingto0,forexample:
1. TypeFM=0<enter>
2. VerifythatthechangewasmadebytypingFM<enter>. The response should be
: fm
0
To View or Change the Drop Out Temperature
Thedropouttemperatureappliesonlyinmode2.Itisdenedasthenumberofdegrees
above the state 1 temperature set point at which the fan will be cut off.
To view the current drop out temperature setting:
1. TypeFT<enter>. The response will be
: ft
1.000
1.000indicatesadropouttemperaturesettingof1°C.
To changethedropouttemperaturesettingto2seconds,forexample:
1. TypeFT=2<enter>
2. VerifythatthechangewasmadebytypingFT<enter>. The response should be
: ft
2.000
Fan Installation and Modes