Manual
The table below indicates which group of terminals applies to each interval for the
various DVSP models. In the drawings which illustrate the different wiring options,
the terminal groupings are chosen purely for convenience: there is no intent in
these drawings to convey any information about specific intervals.
DVSP-2 Interval 1 Relay A
Interval 2 Relay C
DVSP-4 Interval 1 Relay A
Interval 2 Relay B
Interval 3 Relay C
Interval 4 Relay D
2.1 Solenoid Valves
2.11 110 VAC
The steps described below are illustrated in
Figure 2.
1. Supply 110 VAC by connecting the
HOT
terminal to
C
of the appropriate
relay.
2. Connect one wire of the solenoid to the
NEUT
terminal.
3. Connect the other wire of the solenoid to the normally open (
NO
) terminal of
the relay which corresponds to the
C
of Step 1.
2.12 12 VDC
The steps described below are
illustrated in
Figure 2.
1. Supply 12 VDC by connecting
the
+12
terminal to
C
of the ap-
propriate relay.
2. Connect one wire of the sole-
noid to the
GRND
terminal.
3. Connect the other wire of the
solenoid to the normally open
(
NO
) terminal of the relay which
corresponds to the
C
of Step 1.
12 VDC SOLE-
NOID
110 VAC SOLE-
NOID
Figure 2:
12 VDC and 110 VAC solenoids
3