Installation manual

www.desatech.com
118531-01C6
When locating termination cap, it is impor-
tant to observe the minimum clearances
shown in Figure 7, page 8.
If recessing into a wall, you can avoid extra
framing by positioning your replace against
an already existing framing member.
Do not recess termination cap into a wall
or siding.
You may paint the termination cap with
45 F (232º C) heat-resistant paint to
coordinate with the exterior nish.
There must not be any obstruction such
as bushes, garden sheds, fences, decks
or utility buildings within 24" from the front
of the termination cap.
Do not locate termination cap where exces-
sive snow or ice build up may occur. Be
sure to clear vent termination area after
snow falls to prevent accidental blockage of
venting system. When using snow blowers,
do not direct snow towards vent termination
area.
PRE-INSTALLATION PREPARATION
Continued

This direct-vent gas replace heater is pack-
aged with:
one box containing a 4 piece log set located
on the burner in the rebox.
one bag containing the owner’s manual
with installation instructions, operator’s
guide, and warranty information.
one bag of glowing ember material.
one bag of vermiculite hearth treatments.
Remove the shrink-wrap securing the 2 carton
trays to unit. Lift the top carton tray off and
remove 4 corner posts. Discard bottom tray
once unit is moved into position.
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 0"
Perpendicular walls 12"
Floor 0"
Ceiling to louver opening 40"
Front 36"
Top of Standoffs 0"
Vent Surfaces (See venting instruc-
tion for specic venting
clearances.)
Mantel Clearances (See Mantel Clearances,
page 8 for specics on
mantel clearances.)
*Combustible material with a maximum thick-
ness of 5/8" may be ush with the top front
of replace.
    -

    
-

    
     

   





FRAMING AND FINISHING
Figure 4, page 7, shows typical framing of this
replace. Figure 5, page 7, shows framing for
corner installation. All minimum clearances
must be met.
For overall unit dimensions, framing allow-
ances and vent collar locations, see Figure
6, page 7.
For available accessories for this replace,
see Accessories on page 39. If you are using
a separate combustible mantel piece, refer to
Figures 7 and 8, page 8 for proper height and
clearances. You can install noncombustible
mantels at any height above the replace.
Note: Noncombustible mantels may dis-
color!
Figure 3 - Fireplace Bottom Dimensions
15"
36"
25"