Installation manual
www.desatech.com
118531-01C 13
H 
V 
GROUND FLOOR INSTALLATION
Recommended CHVK-58 Corner Horizontal 
Vent Kit:
•  Installation using cabinet surrounds
•  Through  wall  using  square  termination 
(up to 24" horizontal pipe)
•  Corner  installation  (Using  one  6"  vertical 
section, one 90° elbow and a maximum of 
24" of horizontal pipe)
VENTING INSTALLATION
Continued
Figure 14 - Horizontal Termination 
Conguration For Corner Installation 
Using One 90° Elbow
Figure 15 - Horizontal Termination 
Conguration with Vertical Rise and One 
90° Elbow 
51" 6" 26" Max.
57 
1
/
4
" Min. 1' 30" Max.
69 
1
/
4
" Min. 2' 74" Max.
81 
1
/
2
" Min. 3' 98" Max.
94" Min. 4' 122" Max.
106" Min. 5' 146" Max.
159" Min. 9' 20' Max.
TOH
Wall 
Firestop
Straight/
Adjustable 
Pipe 24" Max.
Horizontal 
Square 
Termination
90° 
Elbow
Corner Installation
 
51" Min. 32 
1
/
2
" Max
90° Elbow
Wall 
Firestop
Square 
Termination
Not to Exceed 
(H) Limits
As 
Required 
for (V), 
See Chart 
for Pipe 
Section 
Required
Figures  14 through  18  show  different  con-
gurations and  alternatives for  venting  with 
horizontal termination. Each gure includes a 
chart with critical minimum and maximum di-
mensions which MUST be met. IMPORTANT: 
Remember  that  a  horizontal run  of  venting 
must  have  a  1/4"  rise  for  every  12"  of  run 
toward the termination.
Figure 16 - Square Termination 
Clearance at Ground Floor Installation
12"
Min.