Installation manual
www.fmiproducts.com
108918-01K 5
HEARTH EXTENSION
Ahearthextensionprojectingaminimumof
16"infrontofandaminimumof8"beyond
eachsideofreplaceopeningisrequiredto
protectcombustibleoorconstructioninfront
of replace. Fabricate a hearth extension
using a material which meets the following
specications: a layer of noncombustible,
inorganicmaterialhavingathermalconductiv-
ityofK=0.84BTUIN/FT,HR.F(orless)at1"
thick.For example,if materialselected has
a K factor of 0.25, such as glass ber, the
followingformulawouldapply:
 0.25x1.0"=0.30"thicknessrequired
 0.84
Thermalconductivity"K"ofmaterialscanbe
obtained from manufacturer or supplier of
noncombustiblematerial.Ifhearthextension
istobecovered,usenoncombustiblemate-
rialsuchastile,slate,brick,concrete,metal,
glass,marble,stone, etc. Providea means
topreventhearthextensionfromshiftingand
sealgapbetweenreplaceframeandhearth
extension with a noncombustible material
(seeFigure3).
 WARNING: Hearth extension 
is to be installed only as shown 
in Figure 3.
FIREPLACE INSTALLATION
Continued
Figure 3 - Hearth Extension
SealGap
FireplaceFront
EmberProtector
FireplaceFront
RaisedHearth
FireplaceFront
Elevated
EmberProtector
EmberProtector
SealGap
Hearth
Extension
SealGap
FireplaceFront
EmberProtector
FireplaceFront
Elevated
DoNotBlockLouver
EmberProtector
SealGap
Hearth
Extension
Hearth Extension, Circulating Modes
Hearth Extension, Noncirculating Models
NO