7. Advanced parameters adjustment case:
(1) Case 1: cooling water temperature is controlled by intelligent mode. Requiring
water temperature to be between 25 to 31. Ambient temperature keeping
constant, when the set water temperature is 3 lower than the ambient, the
fluctuation will not exceed ± 0.5 . There will be an alert when water
temperature is 10 lower or higher than target. (e.g. when ambient
temperature is 30.0, cooling water temperature is between 27.5 to 26.5,
if ambient temperature is up to 30.5, water temperature will be between 28.0
to 27.0.)
(2) Case 2: cooling water temperature is controlled by constant mode. Requiring
water temperature is constant in 28, and the fluctuate does not exceed ±2.
The alarm of over high water temperature will be on when water temperature is
5 higher than normal, and the alarm of over low water temperature will be on
when water temperature is 10 lower than normal.
(3) Case 3: cooling water temperature is controlled by constant mode. Requiring
water temperature is constant in 25, and the fluctuate does not exceed ±1.
The over high water temperature will be on then water temperature is higher
than 30, and the alarm of over low water temperature will be on when water
temperature is lower than 10 . (No matter what is the ambient temperature,
the cooling water temperature is constant in 24.0 to 26.0)
Order Code
Item
Value in
case 1
Value in
case 2
Value in
case 3
T-503
Temperature
controller
Factory Setting
T-504
Temperature
controller
Factory Setting
1 F0
Temperature
setting
28 25 25 25
2 F1
Temperature
Difference values
-3 -2 -2
3 F2
Cooling
hysteresis
0.5 2.0 1.0 0.8 0.1
4 F3 Way of control 1 0 0 1 0
5 F4
Alarm for over high
water temperature
10 5 4 10 10
6 F5
Alarm for over low
water temperature
10 10 14
15 15
7 F6
Alarm for over high
Room temperature
45 45 45 45 45
8 F7
Password
8 8 8
8 8
9 F8
The allowed highest
water temperature
31 30 30
30 30
10 F9
The allowed lowest
water temperature
25 5 5 20 20