Instructions / Assembly

11
2.
DZ5200LS-QX Pro
Voltage AC 1P 220V AC 1P 220V AC 1P 110V AC 1P 220V AC 1P 220V AC 1P 110V AC 1P 220V AC 1P 220V AC 1P 110V
Frequency 50Hz 60Hz 60Hz 50Hz 60Hz 60Hz 50Hz 60Hz 60Hz
Current 2.4~3.1A 2.6~3.3A 4.5~6.5A 2.4~3.1A 2.6~3.3A 4.5~6.5A 2.4~3.1A 2.6~3.3A 4.5~6.5A
Compressor
power
0.52KW 0.5KW 0.68KW 0.52KW 0.5KW 0.68KW 0.52KW 0.5KW 0.68KW
0.71HP 0.68HP 0.93HP 0.71HP 0.68HP 0.93HP 0.71HP 0.68HP 0.93HP
Refrigeration
capacity
5084Btu/h 4982Btu/h 5186Btu/h 5084Btu/h 4982Btu/h 5186Btu/h 5084Btu/h 4982Btu/h 5186Btu/h
1.49KW 1.46KW 1.52KW 1.49KW 1.46KW 1.52KW 1.49KW 1.46KW 1.52KW
1281Kcal/h 1256Kcal/h 1307Kcal/h 1281Kcal/h 1256Kcal/h 1307Kcal/h 1281Kcal/h 1256Kcal/h 1307Kcal/h
Refrigerant R-22/R-134a/R-410a
Refrigerant
charge
360g 380g 350g 360g 380g 350g 360g 380g 350g
Precision ±0.3
Reducer Capillary
Protection Overcurrent protection for compressor, flow alarm, over temperature alarm
Pump power 0.03KW 0.05KW 0.1KW
Tank capacity 6 L
Inlet and
outlet
External Ø10mm brass connector Ø10mm speedy connector
Max. lift 16M 27M
Max. flow 16L/min 19L/min
N.W 26Kgs
G.W 29Kgs
Dimension 58 X29X47 cm (L X W X H)
Package
dimension
70 X43X58 cm (L X W X H)
* With heating and higher temperature precision functions are optional.